Parameterizing and Configuring
Parameters
16
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Output after error – 0x45 (69), sub index 0
This parameter defines the behavior of the output in case of an interruption of the IO-Link com-
munication.
Format
Length
Array of Bytes
4 byte
2 bit per channel
The default values are written in
bold
.
Value
Meaning
00
0
Set output to 0
01
1
Set output to 1
10
Current value
Hold current value
11
Reserved
Byte 0
Byte 1
Byte 2
Byte 3
Bit offset
6
4
2
0
14
12
10
8
22
20
18
16
30
28
16
24
Sub index
13
14
15
16
9
10
11
12
5
6
7
8
1
2
3
4
C8P2
(B)
C8P4
(A)
C7P2
(B)
C7P4
(A)
C6P2
(B)
C6P4
(A)
C5P2
(B)
C5P4
(A)
C4P2
(B)
C4P4
(A)
C3P2
(B)
C3P4
(A)
C2P1
(A)
C2P4
(A)
C1P2
(B)
C1P4
(A)
NOTE
This parameter can also be set for all connectors of the module via the IODD.