V02.00 | 2019/10
133
Bit
Meaning
EVT2
Out-of-specification events
An Out-of-specification event in accordance with the IO-Link specification oc-
curred.
GENERR
Common error
The device sends an error (device status 4, in accordance with IO-Link specifica-
tion), which is not clearly specified. Read out the device Event Codes in order to
be able to specify the error more precisely.
HWER
Hardware error
General hardware error or device malfunction.
LLVU
Lower limit value underrun
The process value lies under the parameterized measurement range or the
chosen measurement range has been chosen too high.
OLV
Overload
The connected device detected an overload.
OTMP
Overtemperature
A temperature diagnosis is available on the connected device.
PRMERR
Parameterization error
The connected device reports a parameterization error (loss of parameters, no
parameter initialization, etc.).
ULVE
Upper limit value exceeded
The process value exceeds the parameterized measurement range or the
chosen measurement range has been chosen too low.
VLOW
Undervoltage
One of the voltages at the connected device is below the defined range.
VLOW
Overvoltage
One of the voltages at the connected device is below the defined range.
10.4.3
PROFINET diagnostics
Module diagnostics
(slot 0 according to configuration tool)
PROFINET Diagnostics
Connector
Error code
Channel
Undervoltage V1
-
0x0002
0
Undervoltage V2
-
0x0002
1
DXP diagnostics
(slot 1 according to configuration tool)
PROFINET Diagnostics
Channel
Connector
Error code
Channel
Overcurrent output
DXP1
C0
0x0001
1
DXP3
C1
0x0001
3
DXP5
C2
0x0001
5
DXP7
C3
0x0001
7
VAUX1/VAUX2 diagnostics
(slot 1, according ot configuration tool)
PROFINET Diagnostics
Error code
Channel