ñ
Edi
ti
o
n:
• 25.
10.
20
09
Hans Turck GmbH & Co.KG
ñ
D-45472 Mülheim an der Ruhr
ñ
Witzlebenstraße 7
ñ
Tel. 0208 4952-0
ñ
Fax 0208 4952-264
ñ
ñ
www.turck.com
1/2
ñ
Edition:
Hans Turck GmbH & Co.KG
ñ
D-45472 Mülheim an der Ruhr
ñ
Witzlebenstraße 7
ñ
Tel. 0208 4952-0
ñ
Fax 0208 4952-264
ñ
ñ
www.turck.com
signal processor
MS96 for flow sensors
MS96-11EX0-R/230VAC
●
ATEX category II (1) G, Ex Zone 0
●
ATEX category II (1) D, Ex Zone 20
●
single-channel signal processor
MS96
●
for connection of an intrinsically
safe flow control sensor in zone 0
●
adjustment via potentiometer
●
6 LEDs for display of the flow state
●
intrinsically safe control circuit, [EE-
xia] IIC
●
switch-off delay adjustable in a ran-
ge of 0…25 s
●
wire-break monitoring
●
198…242 VAC
●
change-over, relay output
Wiring diagram
Insertion and inline sensors are supplied
with voltage by the processor devices
which also process and display the measu-
red signals. Devices with MK96…, MS96…
and MC96… housing styles are available.
The individual housing styles are designed
for different operating voltages and feature
various output and supplementary
functions. For intrinsically safe flow sensors
it is required to use signal processors with
intrinsically safe control circuits, i.e. the se-
ries MS96…Ex… and MC96…Ex… .
1
2
6
7
8
3
4
5
9
10
11
12
4BK 16
3BU 15
2WH 14
1BN 13
Flow
Sensor
Pwr
Type
MS96-11EX0-R/230VAC
Ident-No. 5231400
Output function
Two-way contact, relay output
Switching voltage
ð
250 VAC / 60 VDC
Switching current
ð
4 A AC / 0,8 A DC
Switching capacity
cos
ϕ
> 0,7 / L/R < 200 ms
Operating voltage
198… 242VAC
No-load current I
0
ð
28mA
Operating range
dependent on connected sensor
Device designation
É
II(1) G D [EEx ia] IIC
Protection type
[EEx ia] IIC
Ex approval acc. to conformity certificate
TÜV 96 ATEX 1098
No-load voltage U
0
ð
12.6 V
Short-circuit current I
K
ð
200 mA
External inductances/capacitances
L
0
ð
1 mH, C
0
ð
360 nF
Internal resistance R
i
68.5
ò
Housing
terminal chambers, polycarbonate/ABS
Dimensions (w x l x h)
110 x 50 x 75 mm
Attachment
DIN rail (DIN 50022)
Degree of protection (terminals/housing)
IP20 / IP40
Ambient temperature
-20… 60°C
Display 'Setpoint value undershoot '
LED red
Display 'Setpoint value achieved '
LED yellow
Display 'Setpoint value overshoot '
4 x LEDs green
75
110
50