signal processor
MS96 for flow sensors
MS96-11EX0-R/230VAC

ATEX category II (1) G, Ex Zone 0

ATEX category II (1) D, Ex Zone 20

single-channel signal processor 
MS96

for connection of an intrinsically 
safe flow control sensor in zone 0

adjustment via potentiometer

6 LEDs for display of the flow state

intrinsically safe control circuit, [EE-
xia] IIC

switch-off delay adjustable in a ran-
ge of 0…25 s

wire-break monitoring

198…242 VAC

change-over, relay output

Wiring diagram

Insertion and inline sensors are supplied 
with voltage by the processor devices 
which also process and display the measu-
red signals. Devices with MK96…, MS96… 
and MC96… housing styles are available. 
The individual housing styles are designed 
for different operating voltages and feature 
various output and supplementary 
functions. For intrinsically safe flow sensors 
it is required to use signal processors with 
intrinsically safe control circuits, i.e. the se-
ries MS96…Ex… and MC96…Ex… .

1

2

6

7

8

3

4

5

9

10

11

12

4BK 16
3BU 15
2WH 14
1BN 13

Flow

Sensor

Pwr

Type

MS96-11EX0-R/230VAC

Ident-No. 5231400

Output function 

Two-way contact,  relay output

Switching voltage 

ð

   250 VAC / 60 VDC

Switching current 

ð

   4 A AC / 0,8 A DC

Switching capacity 

cos 

ϕ

 > 0,7 / L/R < 200 ms

Operating voltage 

198… 242VAC

No-load current I

0

 

ð

   28mA

Operating range 

dependent on connected sensor

Device designation 

É

    II(1) G D [EEx ia] IIC

Protection type 

[EEx ia] IIC

Ex approval acc. to conformity certificate 

TÜV 96 ATEX 1098

No-load voltage  U

0

ð

   12.6 V

Short-circuit current  I

K

ð

   200 mA

External inductances/capacitances  

L

0

  

ð

1 mH, C

0

 

ð

 360 nF

Internal resistance  R

i

68.5 

ò

 

Housing  

terminal chambers,  polycarbonate/ABS

Dimensions (w x l x h)

110 x 50 x 75 mm

Attachment 

DIN rail (DIN 50022)

Degree of protection (terminals/housing) 

IP20 / IP40

Ambient temperature 

-20… 60°C

Display 'Setpoint value undershoot '  

LED red

Display 'Setpoint value achieved '  

LED yellow

Display 'Setpoint value overshoot '  

4 x LEDs green

75