background image

6

 

/1208

 

Hans Turck GmbH & Co.KG 

 Witzlebenstraße 7 

 45472 Mülheim/Ruhr 

 Germany 

 Tel. +49 (0)208 4952-0 

 Fax +49 (0)208 4952-264 

 [email protected] 

 www.turck.com

Maintenance

If operated in comtaminated or calcareous 
water deposits can build up, which can 
lead to measuring errors. Thus it may 
be necessary to clean the section of the 
sensor through which the liquid passes. 
Please proceed carefully when cleaning 
to ensure that the fl ow channel with its 
sensor elements is not damaged.

Electrical connection (S175)

Operation

The inline fl ow meter has front panel 
buttons for setting functions to display set-
tings. All values are indicated via the 
3-digit 7-segment display.

Button [S1/-]:

 After a short press of 

the button, the set limit value for switch 
point S1 is indicated. In the programming 
mode, this button can also be used to 
decrease the indicated value.

Button [mA/+]:

 After a short press of the 

button, the actual current value in mA is 
indicated. In the programming mode, this 
button can also be used to increase the 
indicated value.

Button [M]:

 After activation the program-

med values are displayed for 3 s. 
In the programming mode, this button 
can also be used to select functions and 
parameters.

Programming

To enter the programming mode, press 
buttons 

[S1/-]

 and 

[mA/+]

 for at least 3 s 

until the display starts fl ashing. For a short 
moment the character string 

[Cod]

 is 

displayed. Followed by the number

[0]

, which can be modifi ed according to 

the valid access code using buttons 

[S1/-]

 and 

[mA/+]

. Use button 

[M]

 to 

subsequently select the required para-
meter. After selection, the parameter is 
displayed for approx. 2 s, followed by the 
associated value which 
can now be modifi ed. During entry it is 
automatically verifi ed whether the set pa-
rameter is admissible. Two decimal points 
of the display will fl ash to warn against an 
invalid entry. To terminate programming 
and save all values press button 

[M]

 for at 

least 3 s until the display stops fl ashing.

–

+

2 WH
4 BK

1 BN

3 BU

I

S1

FC

Access code [Cod]: 

Without entry of an access code it is not 
possible to set or modify device parame-
ters. The ex factory setting is “0”. This 
value can be modifi ed at the end of the 
programming menu.

Adjustable range switch point 
S1 [SP]:

 

The switch point S1 is entered in l/min. 
The switch point may be placed anywhere 
within the total adjustable range (see page 
7 and 10).   

Hysteresis  switch point S1 [hs]: 

The hysteresis is the difference between 
the switch-on value (which is identical to 
the programmed switch point S1) and the 
switch-off value. It is entered in l/min (see 
page 7 and 10).

Output  switch point S1 [OU]:

 

The switching output S1 can be adjusted 
either for the N.O. or N.C. mode.

Switch-on delay  switch point 
S1 [dS]: 

If it is not required to update the output 
signal immediately after the switch point 
S1 has been exceeded, this value can be 
set in a range from 0…50 s. The signal 
will then only be updated after the set 
time has expired, provided the limit is still 
exceeded.

Switch-off delay  switch point 
S1 [dr]:

 

If it is not required to update the output 
signal immediately after the switch point 
S1 has been underranged, this value can 
be set in a range from 0…50 s. The signal 
will then only be updated after the set 
time has expired, provided the limit is still 
underranged.

Average forming [nF

I

]: 

This parameter permits the entry of a 
value which defi nes the time interval 
during which a measuring value average 
is formed. Values between 0…8 s can be 
entered. 
A low value will lead to a fast response, 
whereas a high value steadies the dis-
play of the measuring value. In 0 postion 
the average forming is switched off. The 
average forming has an infl uence on the 
display and the current output. 

Parameter, Operations and Functions

Analogue output [A4] and [A20]: 

These two values determine the fl ow 
range. 

[A4] 

is assigned a minimum value 

in l/min and a current value of 4 mA.

[A20]

 is assigned a maximum value of 

l/min and a current value of 20 mA.
Only a minimum difference of 10 l/min is 
allowed between the two values. In the 
event of an error in the measuring system, 
a current of 2 mA is output.

Reset function [rES]: 

Use the RESET function to set all values 
back to the ex factory settings.  For this, 
the device must be disconnected from 
power. Button 

[M]

 is then pressed during 

re-connection. The character string 

[rES]

 

is displayed. Then you will be prompted 
to enter the access code. Press 

[M]

 to 

confi rm the entry and carry out the reset.

Summary of Contents for FTCI-G1/4A4-D10/L050

Page 1: ...e 7 45472 M lheim Ruhr Germany Tel 49 0 208 4952 0 Fax 49 0 208 4952 264 more turck com www turck com 1 1208 DURCHFLUSS MESSER FCMI FLOW METER FCMI CONTR LEUR DE D BIT FCMI BEDIENUNGS ANLEITUNG INSTR...

Page 2: ...e Magnetic inductive flow meter housing style inline Contr leur de d bit magn tique inductif format Inline Typenschl ssel Type Code Codification H1141 Mechanischer Anschluss mechanical connection conn...

Page 3: ...min Mounting the compression ferrule fitting If no pipe adapters are used then a precision grade pipe meeting the require ments of EN 10305 1 must be used The pipes must feature the diameter and wall...

Page 4: ...Messwertes In der Einstellung 0 ist die Mittelwertbildung ausgeschaltet Die Mittelwertbildung wirkt auf Anzeige und Stromausgang Analogausgang A4 und A20 Diese beiden Werte legen den Durchfluss bereic...

Page 5: ...0 5 8 s Material Sensor A4 1 4571 AISI 316Ti und PVDF A4 1 4571 AISI 316Ti und PVDF Material Prozessanschluss A4 1 4571 AISI 316Ti A4 1 4571 AISI 316Ti Material Geh use PBT PBT Druckfestigkeit 10 bar...

Page 6: ...value can be modified at the end of the programming menu Adjustable range switch point S1 SP The switch point S1 is entered in l min The switch point may be placed anywhere within the total adjustable...

Page 7: ...rammable Switching current 200 mA 200 mA Analogue output 4 20 mA linear 4 20 mA linear Analogue output with defect measuring system 2 mA 2 mA Load RL 200 500 200 500 Measuring tolerance 1 5 l min 0 1...

Page 8: ...in du menu de programmation Plage de r glage du point de com mutation S1 SP Le point de commutation S1 est introduit dans l unit l min Le point de commutation peut se trouver dans l ensemble de la pla...

Page 9: ...O NC Courant de commutation 200 mA 200 mA Sortie analogique 4 20 mA lin aire 4 20 mA lin aire Sortie analogique pour un syst me de mesure d fectueux 2 mA 2 mA Charge RL 200 500 200 500 D rive 1 5 l mi...

Page 10: ...res 4 5 4x 3 100 63 24 53 63 Adapter Adapter Adaptateur Montageplatte Mounting panel Plaque de montage Arbeitsbereich Operating range Plage de fonction l min Ausgangs funktion Output function Fonction...

Page 11: ...um Anschluss 4 Connection 6 Connexion 8 Medien temperatur Medium temperature Temp rature milieu C Umgebungs temperatur Ambient temperature Temp rature ambiante C Schutzart Degree of protection Mode de...

Page 12: ...ans Turck GmbH Co KG Witzlebenstra e 7 45472 M lheim an der Ruhr Germany Tel 49 0 208 4952 0 Fax 49 0 208 4952 264 E Mail more turck com Internet www turck com www turck com D101656 1208 Hans Turck Gm...

Reviews: