Functional Overview
Mounting Instructions
The transducer can be mounted vertically or horizontally using
MB-Q21
Mounting Brackets. The mounting brackets slide in
the grooves on the lower part of the extrusion and clamp down when tightened. It is recommended to use one mounting
bracket on each end and every three feet between. Ferro-magnetic material, (material readily magnetized) should be placed
no closer than .25 inches from the sensing surface of the LDT.
NOTE:
If using the floating magnet option, you must set the automatic gain control.
Automatic Gain Control (AGC)
The Automatic Gain Control feature is only used when sensing a magnet other than the standard
SM-Q21
Slide Magnet. If you
are using the standard slide magnet skip to
Setting ZERO and SPAN Position.
When using the Floating Magnet assembly
FM-Q21
, the magnet should be installed within .375 inches (9.53 mm) of the
sensing surface. The magnet assembly should also be installed in such a manner that it remains an even distance from the
aluminum extrusion throughout the entire stroke. Improperly installed magnets can result in output signal non-linearity.
NOTE:
The north pole of the magnet should be pointed towards the probe.
To set the Automatic Gain Control (AGC) level for the probe, follow these steps:
1. Place magnet assembly close to the dead zone (but within the active region) of the probe.
2. Power down the probe.
3. Short program pin (pin 2) to ground (pin 3).
NOTE:
When the probe is in AGC mode, the output will be either 0 volts or 4 mA, depending on the model that was ordered.
4. Apply power to probe:
a. The LED flashes RED indicating it is in the AGC mode.
b. The LED will change to flashing GREEN when it has determined the proper AGC level and has saved it to
non-volatile memory.
The AGC is now complete.
To place the probe back into the normal operating mode, follow these steps:
1. Power down the probe.
2. Remove short from program pin.
3. Apply power to the probe.
Setting ZERO and SPAN Position
The
Q21 Series
is programmable over the entire active stroke length of the LDT. Keep in mind, there is a 3 inch Null area at the
connector end of the LDT, and a 1.5 inch Dead area at the other end of the LDT where the magnet cannot be detected. The
diagnostic LED can aid you in the setup of the ZERO and SPAN. A green or yellow LED means that the LDT can be programmed
in this area, a red LED means that the LDT cannot be programmed in this area. To set the ZERO and SPAN position for the
probe, follow these steps:
1. Power up the probe in normal operating mode (i.e. program pin floating).
2. Place magnet assembly where
ZERO
is to be located but within the active region of the probe.
3. Momentarily short program pin (pin 2) to ground (pin 3).
4. Place magnet assembly where
SPAN
is to be located but within the active region of the probe.
5. Momentarily short program pin (pin 2) to V+ (pin 1).
NOTE:
A. AGC should be set first before setting the
ZERO
and
SPAN
positions when using a floating magnet
B.
SPAN
could also be set first, followed by setting the
ZERO
position
C.
ZERO
and
SPAN
can be adjusted individually without setting the other
D.
ZERO
= 0 V on 0 to 10 VDC units, -10 V on -10 to 10 VDC units, and 4 mA on 4 to 20 mA units