Warning Symbols Used in the Manual
The indications regarding safety are highlighted using the following symbols:
Attention - Danger
Warning - Generic
Risk – Hazard
Electric Current
Dispose of according to the WEEE Waste Electrical
and Electronic Equipment Directive
Installation regulations and warnings
▪
Protect the equipment from direct exposure to sunlight.
▪
Position the equipment away from sources of heat or electromagnetic fields generates by
equipment being used.
▪
Fix the equipment to the wall at a height of at least 60 cm from the ground; it must be clearly
visible and easy to reach.
▪
Connect the equipment to supply lines different to those used for motor drives or other large
power devices that could generate network disturbances or instability.
▪
The appliance electric power supply must be protected by a 230Vac~ 30 mA differential circuit
breaker and a 230Vac~ 10 A bi-polar magnet circuit breaker, positioned in a place that is easy to
reach.
▪
Before intervening on the appliance to perform any operation, deactivate the magnet circuit
breaker.
▪
For electrical operations, always remove the voltage and wait 30 seconds for the internal capacitors
to discharge before opening the container.
When finished, close the device before turning on power.
▪
Make sure you are in a safe atmosphere before using the equipment for any type of operation.
▪
Use flame-proof cables with minimum section of 0.75mm² certified and compliant with regulations
to connect the power supply voltage.
IEC60227
IEC60245
▪
Use flame retardant cables with a minimum section of 0.5 mm² for all input control signals and
valve actuators.
▪
Use flame retardant cables with a minimum section of 0.75 mm² for signal relay contacts.
▪
The protective earth cable must be yellow/green.
▪
The protective earth cable must be connected first.
▪
The yellow/green cable must only be used for earthing.
Continues....