18

automatically after 3 minutes when power returns. 

If the memorization condition is forced cooling mode, the unit will run in cooling mode for 30 minutes 

and turn to auto mode as 24    (75.2    ) setting temp.

 

6.4.10 Ionizer/Plasma dust collector function (optional) 

The indoor unit is equipped with Ionizer, which is controlled by the CLEAN AIR button on the remote 

controller. When the unit is turned on, press the CLEAN AIR button to activate the function. Press it 

again to stop the function. During the time when Ionizer is controlled by remote controller, Ionizer will 

be turned off automatically if indoor fan stops running due to malfunctions or anti-cold-wind. When 

indoor fan restarts after malfunctions being eliminated and anti-cold-wind being released, Ionizer will 

be available again. 

6.4.11 Mode conflict 

The indoor units can not work cooling mode and heating at same time.   
Heating mode has a priority. 
6.4.11.1 Definition: 

 

Cooling mode 

Heating Mode 

Fan 

Off 

Cooling mode 

No 

Yes 

No 

No 

Heating Mode 

Yes 

No 

Yes 

No 

Fan No  Yes 

No 

No 

Off No  No 

No 

No 

No: No mode conflict; 
Yes: Mode conflict 
6.4.11.2 Unit action 

z

 

Suppose Indoor unit A working in cooling mode or fan mode, and indoor unit B is set to heating 
mode, then A will change to stand by and B will work in heating mode. 

z

 

Suppose Indoor unit A working in heating mode, and indoor unit B is set to cooling mode or fan 
mode, then B will change to stand by and A will be no change. 

 

Summary of Contents for TAS-09MVHN

Page 1: ...VMI 1102 A SERVICE MANUAL AIRCONDITIONER DC INVERTER MULTI TYPE MSV1I 09HRDN1 M TAS 12MVHN INDOOR VERTU DC INVERTER MULTI SERIES TAS 09MVHN...

Page 2: ...ion 1 1 1 Safety Precaution 1 1 2 Warning 1 2 Function 6 3 Dimension 7 4 Wiring Diagram 8 6 Electronic function 10 6 1 Abbreviation 10 6 2 Display function 10 6 3 Main Protection 11 6 4 Operation Mode...

Page 3: ...the product there is risk of fire or electric shock Always ground the product There is risk of fire or electric shock Install the panel and the cover of control box securely There is risk of fire of e...

Page 4: ...of fire or electric shock Do not place anything on the power cable There is risk of fire or electric shock Do not plug or unplug the power supply plug during operation There is risk of fire or electri...

Page 5: ...product damage Ventilate the product from time to time when operating it together with a stove etc There is risk of fire or electric shock Turn the main power off when cleaning or maintaining the pro...

Page 6: ...or loss of property Do not block the inlet or outlet of air flow It may cause product failure Use a soft cloth to clean Do not use harsh detergents solvents etc There is risk of fire electric shock or...

Page 7: ...ent types of batteries There is risk of fire or explosion Do not recharge or disassemble the batteries Do not dispose of batteries in a fire They may burn of explode If the liquid from the batteries g...

Page 8: ...peration mode high med low breeze auto Indoor unit Operation by remote controller Sensing by temperature sensor Room temperature control Anti freezing control in cooling Time Delay Safety control Indo...

Page 9: ...Dimension of installation hole 795 mm 31 30 inch 270 mm 10 63 inch 165 mm 6 5 inch 165 mm 6 5 inch 165 mm 6 5 inch TAS 12MVHN 845 mm 33 27 inch 286 mm 11 26 inch TAS 09MVHN TAS 12MVHN 160 mm 6 28 inch...

Page 10: ...8 4 Wiring Diagram Indoor unit TAS 09MVHN TAS 12MVHN...

Page 11: ...the unit to function abnormally 2 Room relative humidity less than 80 If the air conditioner operates in excess of this figure the surface of the air conditioner may attract condensation Please set t...

Page 12: ...operation CLEAN AIR display optional Illuminated when Ionizer is activated TURBO operation display Illuminated when select TURBO function in cooling operation or in heating operation DIGITAL DISPLAY...

Page 13: ...r certain time the unit will stop and the LED will display the failure 6 3 3 Indoor fan delayed open function When the system starts up the louver will be active immediately and the indoor fan will op...

Page 14: ...e is the same as auto fan in setting temperature 6 4 2 Cooling Mode 6 4 2 1 Compressor running rules The compressor will run at corresponding frequency according to the gross amendatory capacity deman...

Page 15: ...eed can be selected as high medium low and auto Auto fan in cooling mode acts as follow 6 4 2 3 Evaporator low temperature T2 protection When T2 4 39 2F the indoor has no capacity demand and resume ti...

Page 16: ...HEAT _F2 HEAT _F11 HEAT _F12 Amendatory capacity demand 0 1 2 11 12 6 4 3 2 Indoor fan running rules Indoor fan speed can be set as high medium low or auto fan and the anti cold wind function is pref...

Page 17: ...g If any one of following items is satisfied defrosting will stop and the machine will turn to normal heating mode T3 TCDE TCDE 15 The defrosting time achieves 10min 6 4 4 Auto mode This mode can be c...

Page 18: ...the AC will run as below sequence When the machine is off pressing the touch button will carry the machine to forced auto mode after this if pressing the button once again the machine will turn into...

Page 19: ...leep function mode 6 4 8 1 Operation time in sleep mode is 7 hours After 7 hours the AC quits this mode and turns off 6 4 8 2 Operation process in sleep mode is as follow When cooling the setting temp...

Page 20: ...nning due to malfunctions or anti cold wind When indoor fan restarts after malfunctions being eliminated and anti cold wind being released Ionizer will be available again 6 4 11 Mode conflict The indo...

Reviews: