31 SERVICE MANUAL FOR AMERICA
Function of Inverter indoor unit
一、summary
1.
This control is use for DC Multi-Spilt air conditioners.
2.
Power of indoor unit supply is 220-240V/50Hz, voltage range is 170V~270V.
3.
Control precision of indoor temperature is ±1.8
O
F.
4.
Indoor fan motor is PG motor.
5.
Control accord with :
GB5956-91《safe requirement of air conditioner》
GB7725-2004《air conditioner》;GB3797-87《control equipment of electrical equipment》
Vibrancy test:frequency 50Hz,acceleration 2.5g
PCB ought to accord with GB4588.1 and GB4588.2
Electromagnetism compatibility ought to accord with relate standard of nation.
二.Base parameter
1.
Use condition:ambient temperature 5
O
F~185
O
F, relative humidity =30-95%.
2.
Receive distance of remote:<10m
3.
Angle of remote:<120 degree
4.
Control precision of temperature: ±1.8
O
F
5.
Speed precision of indoor fan motor: ±10RPM
6.
Time precision: <0.1%
三.Major function of control
1.
Remote
Turn on/off
Mode select
auto
cooling
dehumidify
heating
ventilation
Indoor fan speed select
manual mode: high, middle, low speed
auto mode: accord difference of indoor room temp. and set temp. automatic select.
Temperature setting
Cooling: 60
O
F――90
O
F, default is 77
O
F
Heating : 60
O
F――90
O
F, default is 77
O
F
Dehumidify: default is 77
O
F and it can’t adjust.
Auto: default is 77
O
F and it can’t adjust.
Ventilation: 60
O
F――90
O
F, default is 77
O
F
Sleeping
It can set or cancel 24HR sleep .
Timer on or timer off
Timer can set 24HR on or off.
Air flower control.
Turbo running
Hold key
2.
Main PCB board