background image

NOTE: All detection devices connected to an individual
circuit must be of the same type.

Detection Zones and Zone Expansion

(The CPA6 has six zones. Each zone may have one
circuit only, or can, by the addition of external Zone
Expansion Modules, (Z.E.M.’s) be expanded in
increments of two circuits, up to a maximum of ten (see
figure 1).

Z.E.M’s are housed in small tamper-protected
metal/plastic enclosure and would normally replace a
junction box in the location of the detectors.

The enclosure tamper switch is connected into loop ‘A’
of a Z.E.M. internally.

Two different types of detection circuits may be
connected to a single Z.E.M and each identified during
the commissioning procedure.

Z.E.M’s are interconnected with two wires, the output of
one Z.E.M. connecting to the input of the next. Up to

five

Z.E.M.’s can be connected in this manner into a single
CPA6 zone input.

Circuit identification is achieved by noting the position of
each Z.E.M. in its associated group e.g. Zone 4 circuit 6
refers to the circuit connected to the ‘B’ loop of the third
Z.E.M. on the input to Zone 4 of the panel.

NOTE: Z.E.M. Interconnection is polarity conscious.

When a Zone has only a single circuit wired to it, the
Z.E.M. -ve input connection on the CPA6 PCB is ignored
and the +ve & -ve terminals are used for the detection
circuit, with the E.O.L. terminals providing the end of line
resistor.

Detection circuit wiring to Z.E.M.’s is via terminals ‘Loop A’
and ‘Loop B’ and the E.O.L. resistors must be remote
from the Z.E.M fitted.

Outputs

P.A.

This drives high (to + 12V via a 47R resistor) for
signalling purposes following activation of any
P.A. circuit.

ALARM

This drives high (to + 12V via a 47R resistor) for
signalling purposes following activation of any
detection circuit (

excluding P.A. Circuits

) when

the system is set.

SET

This drives high (to + 12V via a 47R resistor) for
signalling purpose when the alarm system is
set. The output is removed as entry to the
premise commences.

E/E

This drives high (to + 12V via a 47R resistor) when
the system is being set or opened.

24HR/FAULT

This output drives high (to +12V via a 47R resistor)
following operation of 24 hour or tamper circuits
during the day, or any fault condition during
system setting.

BELL RELAY

This output is a voltage-free normally open relay
contact which closes an alarm, following any
programmed bell delay. The contact will
remain closed until either the alarm system is
reset, or a pre-set bell duration time expires.

NOTE: When the panel supply is switched via the relay
contacts to drive an external bell, the bell must be of a
‘suppressed’ type.

AUX SUPPLY

This output is individually fused (FS1) and
provides 13.6 volts dc @

300mA (max) for

external equipment.

SPEAKER

This output drives the integral sounder speaker,
but may also be used to drive an additional
extension speaker (8 Ohm) where required.

CPA6

4 of 16

496524 Issue A

CPA6

Summary of Contents for CPA6

Page 1: ...CPA6 Installation User Guide Compatible Equipment CPA6 OM Output Module 9040 Loudspeaker DC54 58 Digital Communicators Stand Alone Only 496524 Issue A 1 of 16 CPA6...

Page 2: ...ection circuits may be connected 10 per zone interfaced via remotely positioned Zone Expansion Module or ZEM ENGLISH TEXT DISPLAY Provides fully detailed information of system status detection circuit...

Page 3: ...en the system is in the test set condition this definition is used TYPE 2 24 hour Circuit This type is selected when continuously monitored detectors are connected typically fire doors tube and wire f...

Page 4: ...nals providing the end of line resistor Detection circuit wiring to Z E M s is via terminals Loop A and Loop B and the E O L resistors must be remote from the Z E M fitted Outputs P A This drives high...

Page 5: ...CLK 0 Loop A Loop B 0 CLK CLK 0 Loop A Loop B 0 CLK 2 off connectors for use as Junction Block for 12V auxiliary supply 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 NOTE Up to Z E M s may be fitted to zone...

Page 6: ...ain Audible L P A Alarm O P Main Audible L TYPE 5 EXIT ENTRY CIRCUIT 24Hr Fault O P Fault Audible NL SHUNTED BY PANEL Main Alarm O P Main Audible L SHUNTED BY PANEL TYPE 6 LAST EXIT SHUNT LOCK CIRCUIT...

Page 7: ...SE 2 Is rated at 1A and is of the Anti Surge type Its function is to protect the supply to the CPA6 circuitry from overloads Failure of FS2 will result in the CPA6 display blanking and the keypad tone...

Page 8: ...of the year Enter the month number of the year via the keypad 01 JANUARY etc As keys are pressed the display will show the month number When this is correct press the YES ENTER key Enters the display...

Page 9: ...number of detection circuits that the panel identifies on Zone 2 REPEAT STEP 21 FOR ZONES 2 TO 6 The display shows the number of detection circuits that the panel identifies on the last Zone Zone 6 Co...

Page 10: ...t by subscriber or by Engineer into memory and initiates the next step of commissioning The routine first assumes that P A alarms operate the main alarm audibles following a preset delay during the sy...

Page 11: ...ER key operated If entry to the premises is to be timed then enter the required entry time in seconds via the keypad Registers that the alarm system has infinite entry time As keys are pressed the dis...

Page 12: ...r information from the keypad The P A Code is a 4 digit keypad code which whenever operated activates the panels P A output The Code is particularly useful to a subscriber OPENING the alarm system und...

Page 13: ...ers User code x in the panel s memory Selecting this User routine will enable the alarm system to be fully tested and set opened by the Engineer without knowledge of any user Code The commissioning ro...

Page 14: ...nly if this facility has been programmed 1 Ensure that all monitored areas except those to be shunted excluded are secured 2 The panel display should show the date and time and System Open 3 Enter you...

Page 15: ...panel display will show Do you want to set the system 4 Press NO The display will show Do you want Tests Press YES ENTER 5 The display will show Do you want Bell Test 6 Press YES ENTER The display wil...

Page 16: ...CPA6 CPA6 16 of 16 496524 Issue A This page intentionally left blank...

Reviews: