Tunstall 68005/96 User & Installation Instructions Download Page 2

User/Installation Instructions for Radio Smoke Detector 

 

Model Number: 68005/96

 

 

D6707324A1 

 

Seite 2 von 4 

 

 

 

Wireless Transmitter Module (869MHz) 

The  Smoke  Detector  is  equipped  with  a  wireless  869MHz  transmitter 
module.  This  will  transmit  alarm  signals  via  Tunstall  Emergency 
equipment to monitoring centres. 

Function test 

Attention:  The  smoke  detector  generates  a  very 
powerful  and  shrill  tone  which  can  be  harmful  to 
your  ears.  Please  keep  at  least  a  distance  of  50  cm 
during the function test. 

 
Perform the function test every month. Proceed as follows: 
 
1.  Check if the LED is flashing. 
2.  Press the fibre-optical button for at least 1 sec.: If a signal tone is 

generated,  the  detector  works  properly.  If  no  signal  tone  is       
generated, please replace the batteries. 

 

 

 
 

3.  If after replacing the batteries a tone can still not be heard then the 

smoke detector is damaged and has to be replaced by a new one. 

 

Programming to Tunstall equipment 

 

Register  the  radio  smoke  detector  to  Tunstall  emergency  equipment 
by  placing  the  emergency  equipment  in  trigger  registration mode  and 
pressing the fibre-optical button for at least 1sec. A signal tone is gen-
erated  and  the  detector  transmits  a  radio  message  to  the  emergency 
equipment.  Check  that  the  registration  is  successful  by  pressing  the 
fibre-optical button again to raise an emergency call. If no alarm is giv-
en, please check the following: 

 

Battery state? 

Smoke detector faulty?  

Emergency equipment within radio range?  

Emergency equipment programming correctly? 

Self-test and battery test 

The smoke detector identifies smoke at an early stage of development.  
An  independent  self-test  permanently  controls  the  function  of  the 
smoke evaluation. Possible faults are shown per alarm signal  
(signal tone or light diode). The power supply is continuously checked 
through  the  battery  test.  If  the  battery  voltage  decreases  under  a  de-
fined  point,  the  smoke  detector  signals  30  days  long  that  the  battery 
should  be  replaced.  The  smoke  detector  continues  to  function  fully 
during these 30 days, however the battery should be replaced as soon 
as possible. Life time of the battery: approx. 10  years (using U9VL-J-
P).  Check  the  functionality  of  the  smoke  detector  after  a  battery 
change  by  pressing the  fibre-optical-button [item  2 function  test]  for  a 
few seconds. 

Alarm muting 

The alarm muting can be activated by pressing the fibre-optical button. 
The  smoke  detector  will  mute  for  approximately  10  minutes  and  then 
reset itself to normal operation. 

Serial number to be found on the “type label” 

 
 
 
 
Replace  all  smoke  detectors  after  10  years.  The  recommended  ex-
change date is located on the label of the smoke detector!  
 

 

Operation- and alarm signals 

 

Signal 

Meaning 

Signal tone 

LED 

No Tone 

Flashes each 40 s 

Automatic 

self-test, 

regular operation mode 

Loud 
interval tone 

Flashes 

Local  smoke  alarm  or 
function test 

Short signal tone 
each 40 s 

Flashes  alternating  with 
signal tone 

Failure / pollution 

Short signal tone 
each 40 s 

Flashes  parallel  to  signal 
tone 

Indication  for  battery 
replacement 

No Tone 

Flashes every 10 s 

Alarm muting 

No Tone 

Flashes 3x every 43 s 

Alarm  memory  (alarm 
in the previous 24 h).  
Cleared  by  pressing 
fibre-optical button

.

 

Maintenance 

A maintenance service should be provided every 6 months (or in case 
of a failure message) in order to guarantee the operating safety of the 
smoke detector over a long period. 

 

To carry out this service please proceed as follows: 

-  Remove  the  smoke  detector  from  the  base  (turn  counter  clock-

wise) and clear away the dust. 

-  Wipe the smoke detector with a damp cloth. 
-  Place the  smoke  detector  back  in  the  base  and  turn  it  clockwise   

until it is locked. 
Note:  the  smoke  detector  will  not  engage  inside  the  base 
without the battery inserted. 

-  Check  if  the  automatic self-test  (smoke  detector flashes  approxi-

mately every 40 seconds) is executed. 

-  Perform a function test. 

Meaning of symbols 

 

    

The crossed-out refuse container on this product 
indicates that it should not be disposed with other 
business  waste  at  the  end  of  its  working  life.  To 
help  ensure  that  valuable  resources  are  reused 
and recycled and to prevent possible harm to the 
environment.  

    

 

Product-Approval  according  to  EN  14604  and 
VdS  2344  by  the  VdS  Schadensverhütungs 
GmbH. 

Technical data 

Detection method: .................................................... Tyndall-effect 
Operating voltage: .............................................................. 9V DC 
Alarm indication: ............................................. optical and acoustic 
Class of protection: ..............................................  EN 14604:2005 
Battery to be used with wireless module:  .......... Ultralife U9VL-J-P  
Average lifetime of the U9VL-J-P battery @15-20ºC: ....... 10 years 
Operating temperature range: .................................... -10 to+60 °C 
Max. monitored area: ...................................... 60 m² till 6 m height 
Indicator: .......................................................................... red LED 
Signal tone: ............................................................. >85 dB(A)/3m 
Dimensions without base (Ø x H):...........................100 x 35,0 mm 
Dimensions with base (Ø x H): ...............................100 x 51,0 mm 
Mounting hole distance on base: ........................... 28,0 - 65,0 mm 
Housing material/colour: ................................................ABS/white 
Wireless range: ................................................ Typically 25 - 50m 
Detector Life: ................................................................... 10 years 
VdS Approval: ............................ G 202042 and 0786-CPD-20681 
D of C………….......uk.tunstall.com/media/resources/literature 
 
CE Approval: ....................................................................  marked 
Please contact:  
 
 
 
 

smoke inlet apertures 

fibre-optical button 

Tunstall Healthcare (UK) Ltd

 

Whitley Lodge

Whitley Bridge

Yorkshire, DN14 0HR, UK

+44 1977 661234

www.tunstall.co.uk

e-mail: [email protected]

 