TTL air curtain systems - Control and automation panel UBT
plus
20
8. Menu guidance - menu tree (cont.)
Main menu point
Nr.
Submenu
Function
Parameter / Default
5 Blowout temperature controller AIR
1
WATER nom. standby
3UHVHOHFWLRQWHPSHUDWXUHÁRZPD[
20-80 (°C)
40
2
AIR nom.
Preselection blow-out temperat. (max.) 20-80 (°C)
32
3
Controller KP
Adjustment controller parameter
1..250 (see p. 32)
20
4
Controller KI
Adjustment controller parameter
1..250 (see p. 32)
20
5
Controller KD
Adjustment controller parameter
0..250 (see p. 32)
20
6
AIR contr. SUMMER ON
blow-out temp. contr. SUMMER mode 0=NO / 1=YES
0
7
Setback WINTER ON
Temperature setback mode winter
0=NO / 1=YES
0
8
Setback -start °C
Temperature start value for tempera-
ture setback mode
0-30 (°C)
21
9
Setback -scaling
Relationship setback value - outside v.. 1-100 (= 10,0 °C)
10
10
Overwrite contr.valve
Overwrite of the valve setpoint,
selection of avalve fracture opening
(opening by hand for testing purpose)
0-100 (%)
0
11
Overwrite -time
Overwrite of the valve setpoint,
selection of a remaining time till return
to the controlling process
(opening by hand for testing purpose)
1-10 (min)
1
4 Analogue input
1
92/YLDH[W9
External control of volume controller 0=OFF
1=GLOB. / 2=LOC.
0
2
Recess limit
Damping for controller values in case
of return from external controlling to
internal controlling
0 (%)
0
3 Basic settings(cont.)
14
Operation mess. active
Switch over for operation message
„Ready for operation“ or „Operation“
0=NO / 1=YES
1
15
°C active
Display of temperatures at main display
0=NO / 1=YES
0
16
7LPHÀOWHUFKDQJH
9DOLGRSWLPHXQWLOQH[WÀOWHUFKDQJLQJ
0=OFF / 1-10000 (h) 288