Standalone Alarm Unit For Hydrocarbon Leak Detection Sensor

Installation Notice

FG-STAD

Installation

Notice 

FG-STAD 

1

2

Application

  

As the unit is powered permanently, all wiring connections 

must be made away from explosive atmospheres. The 

unit should be grounded correctly to earth to avoid static 

electricity issues.

  

As the unit housing contains aluminum, it is considered a 

potential risk of ignition by impact or friction. Care must be 

taken to prevent impact and friction during installation and 

use.

 

The ambient temperature range is from -30°C (-22°F) to 

80°C (175°F).

         

Conditions for installation and  

maintenance

   

FG-STAD stands for "standalone alarm unit for hydrocarbon 

leak detection sensors". This unit can be connected with one 

hydrocarbon sensor only, and by TTK SAS.

  

This equipment can be installed in explosive atmospheres in 

accordance with Directive 94/9/EC. The surface temperature 

must not exceed the value shown below.

CAUTION

 

Please read all the instructions in this manual carefully 

before installation. Do not start installation before reading 

these instructions.

 

This equipment may receive some hazardous voltages. 

Failure to read these instructions may lead to serious injury 

or material damage. Before setting up the installation, check 

that both the model and power supply suit your application.

 

This equipment must be wired in accordance with standard 

practice by qualified staff.

  

INPUT SENSOR: This input will work only with a TTK 

hydrocarbon detection sensor.

  A: To connect with the GREEN wire (use with FG-ODP 

probe sensor only)

  B: To connect with the WHITE wire (of FG-CLOD: Leader 

cable for OD BUS)

  C: To connect with the BLACK wire (of FG-CLOD: Leader 

cable for OD BUS)

  D: To connect with the RED wire (of FG-CLOD: Leader 

cable for OD BUS)

  

SWITCH OUTPUT: 

  CH1+: Channel one positive
  CMN: Common
  CH2+: Channel two positive
  CMN: Common

Mounting

3

Figure 1: Input sensor and output terminal block connection

  

UNIT ON-OFF SWITCH:

J4: To be moved to ON    

(internally) position to 

power-on the unit