background image

1

  

 

FG-ALS 

Alarm Locating Unit

 

Installation Instructions 

The FG-ALS Alarm Location Unit is designed to be used with two kinds of TTK analogue sense cables: random FG-ECS, FG-ACS 
and pre-connected sense cables FG-ECX, FG-ACX. It allows the leak detection and location of liquids. 
The appearance of a fault (leak, cable break) is detected in the following way: 

 

An audible alarm is triggered; 

 

A luminous diode turns on; 

 

A dry contact is activated to transfer the alarm information to remote monitoring equipments. 

 

JBUS/MODBUS protocol is communicated to BMS. 

 

The display on the front face shows the leak location (in metre). 

To stop the audible alarm, press the “reset” button.  The diode and the dry contact remain activated as long as the fault is  pre-
sent. When the fault disappears, the diode switched off, the relay returns to its original normal status and the content of the 
display disappears. 
The maintenance of the system is recommended for every six months minimum. 

1. 

Fixing the FG-ALS Alarm Location Unit 

The FG-ALS Alarm Location Unit is available in wall mounted version (165 x 85 

x 55 mm). 

Two  of  the  three  cable  glands  are  placed  on  the  FG-ALS  Alarm  Unit,  the  last 

one can be screwed in the place of plug PG7.   

Use the two fixing holes in the lower part of the unit box. Release the higher 

part of the box of the lower part which is maintained by two screws. These two 

parts  could  be  easily  dismounted  after  mural  fixing.  Withdraw  carefully  the 

higher part with the PCB (printed circuit board). 

 

FG-ALS Alarm Locating Unit Description

 

FG-ALS Alarm Locating Unit Installation 

2.  

Connection and Adjustment 

2.1 Power Connection 

FG-ALS Alarm Unit is powered into 230-240 VAC only. 
The maximum section of the cable is of 14 AWG for 230-240 VAC. Use PG9 cable gland for the 
cable 230 V.  

2.2 Connection of the  

Dry Relays 

The dry relays are free of potential.  The maximum section of the cables is of 18 AWG. 

Dry Contact for Leak:  

The leak contact transfers the information of leak to a PC (or supervisor), allowing automated 
equipment control. 

Dry Contact for Cable Break: 

A specific contact is activated in case of cable break. A power supply failure also activates this 
contact. 

Relay of Leak and Relay of Cable Break:   

Simple relay:  COM-NO-NC 
Max. commutated Voltage: 125 VAC / 60 VDC  

2.3.Serial Interface  

Physical Support  

Opto-isolated, Two-Wire RS485  

2.4. Serial Link Parameters  

9500 Baud, 8 Data Bits, 1 bit Stop, no Parity  

2.5. Supported Protocol  

Modbus, Functions 3 and 4  

2.3. Adjustment of the 

Detection Sensitivity 

You can adjust the detection sensitivity, using the potentiometer (P1). The adjustment factory 
corresponds to the maximum sensitivity (1 turn). 

FG-ALS Alarm Locating Unit Installation Instructions v1.5-092014 

The FG-ALS Alarm Location Unit  
wall mounted version contains:   

 

1 FG-ALS Alarm Unit: 230VAC/50Hz 

 

3 PG cable glands: 2 PG7 + 1 PG9  

 

1 Installation Instructions 