TTK FG-ALS Installation Instructions Download Page 2

2

  

 

1. 

Connection of Sense Cables FG-ECS or FG-ACS 

A junction with a length of 3.5 metres of Belden jumper cable on each length of FG-ECS and FG-ACS, allows a simple connection 
to the FG-ALS alarm locating unit. 
 
 
 
 
 
 
 

2.  

Connection of Sense Cables FG-ECX or FG-ACX  

 
 
 
 
 
 
 
 
 

Sense Cables Connection

 

Caution: All connections of the connector blocks must be done with FG-ALS Alarm Locating Unit supply switched off.  

Material recommended (*) for a complete installation with FG-ALS Alarm Locating Unit: 

FG-ALS Alarm Locating Unit Installation Instructions v1.5-092014 

To connect the various cables (leader cable, power supply and relays) at 
the corresponding connector block. 

    

Power supply 230VAC/50Hz 

P : Live

 

N : Neutral

 

   : Earth 

Leak Relay 

1: NO

 

2 : COM

 

3 : NC 

Cable Break Relay 

1 : NO

 

2 : COM

 

3 : NC 

RS485 

1: COM

 

2 : RT+

 

3 : RT- 

FG-ECS or FG-ACS

 

or FG-ECX or FG-ACX 

A : Green wire

 

B : White wire

 

C : Black wire

 

D : Red wire 

Potentiometer (in blue colour) P1 for adjusting sensitivity of detection 

FG-ALS

  Wall Mounted Alarm Location Unit 

FG-ECS

  Water Sense Cable Cut to Length in Roll of 400m 

FG-ACS

  Acids Sense Cable Cut to Length in Roll of 400m 

FG-ECX15/7/3

  Water Sense Cable in 15/7/3m 

FG-ACX15/7/3

  Acids Sense Cable in 15/7/3m 

CFC100

  Hold-down Clips and Adhesive (Set of 100) 

ES-EC

  Signal Tags (Set of 40) 

To connect the FG-CLC leader cable, refer “FG-SYS installation guide” chapiter 1, sector 3.3 “Connection of FG-CLC leader ca-
ble”. 
The FG-CLC leader cable, connected to the FG-ALS alarm unit with a female connector, at its extremity. The beginning of the 
sense cable thus corresponds at its extremity with a male connector. 
Connect the first sense cable to the leader cable, coming from the FG-ALS alarm unit. 

SOU

   

  
  
 

Leak 

  

FG-

                 

Female connector 

Male connector 

End termination 

Sense cable FG-ECX/ACX 

Sense cable FG-ECS/ACS random 

Jumper cable 

Sense Cable 

P   N   

ON 

Leak Relay 

Cable Break 
Relay 

      

Modbus Slave N°

 

TTK FG-ALS 

TTK - FRANCE 

RS485

1 2   3  4  5  6  7  8  

Potentiometer 