6 Electrical Connection
6.1 PV connection
TSOL Inverter can be connected in series with 2-strings PV modules for 3.0kW, 3.7kW,
4kW, 4.6kW ,5kW and 6kW.
Select PV modules with excellent function and reliable quality. Open-circuit voltage of
module arrays connected in series should be <Max. DC input voltage; operating voltage
should be conformed to MPPT voltage range.
M ax. DC Voltage Limitation
Model
TSOL-H
3.0K-H
TSOL-H
3.6K-H
TSOL-H
4.0K-H
TSOL-H
4.6K-H
TSOL-H
5.0K-H
TSOL-H
6.0K-H
Max. DC voltage[V]
620
MPPT Voltage Range(V)
100-560
Note
!
Please choose a fitting external DC switch if the model (N version) is
purchased.
The following requirements of PV modules need to be applied for each
input area;
- Same type - Same quantity - Identical alignment - Identical tilt
Please do not make PV positive or negative ground!
In order to save cable and reduce the DC loss, we suggest to install the
inverter near PV modules.
Warning!
PV module voltage is very high, which already achieve dangerous voltage
range, please comply with electric safety rules when connecting.
Please do not make PV positive or negative ground!