20
Pa
rt
Two
CONFIGURE MENU
MENU ITEM
SOFTWARE NAME
ITEM DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
ROOM
VOLUME
ROOM VOLUME
The ROOM VOLUME item is used to input the volume of the
room. The room volume is required to calculate air changes
per hour.
Entering a value for the volume will add the air changes per
hour value to the display’s scrolling sequence. If a zero value
is entered the air changes per hour will not scroll on the
display.
If the DIM displays English units, area must be entered in cubic
feet. If metric units are displayed area must be entered in cubic
meters.
The air change per hour is calculated using the ROOM
VOLUME and the input from the air flow station. If no flow
station is installed, a zero value should be entered.
0 to 20,000 cubic
feet
(0 to 550 cubic
meters)
The DIM does
not compute
volume. The
volume must be
first calculated
and then entered
into the unit.
0
ACCESS
CODE
ACCESS CODE
The ACCESS CODE item selects whether an access code
(pass code) is required to enter the menu. The ACCESS
CODE item prevents unauthorized access to a menu. If the
ACCESS CODE is
ON or OFF
OFF
ON a code is required before the menu can be entered.
Conversely if the
ACCESS CODE is OFF no code is
required to enter the menu.
END OF MENU
The END OF MENU item informs the user that the end of a
menu has been reached. The user can either scroll back up
the menu to make changes, or press the
SELECT
or
MENU
key to exit out of the menu.