Chapter 3

 

Log Interval 

The logging interval is a frequency period that the 
instrument will log readings. For example, if the 
logging interval is set to 30 minutes, each sample 
will be the average of the last 30 minutes. 

Menus 

DISPLAY SETUP

 

Display setup menu is where you will setup the desired parameters to 
be displayed on the running screen. With a parameter highlighted you 
can then use the 

ON

 soft key to have it show up on the running 

screen or select the 

OFF

 soft key to turn off the parameter. Use 

PRIMARY soft key to have a parameter show up on the running 
screen in a larger display. Only one parameter can be selected as a 
primary, and up to 2 secondary parameters can be selected at one 
time. 

PRESSURE ZERO 

To zero the pressure reading, select the Pressure Zero menu. The 
instrument will indicate if the pressure zero was successful. 

SETTINGS

 

Settings menu is where you can set the general settings. These 
include Language, Beeper, Select Units, Time Constant, Contrast, 
Set Time, Set Date, Time Format, Date Format, Number Format, 
Backlight and Auto Off. Use the 

 or 

 soft keys to scroll through the 

settings for each option and use the 

  

key to accept settings. 

FLOW SET UP

 

In 

Flow Setup

 mode, there are four types: Round Duct, Rectangle Duct, 

Duct Area, and K-Factor. Use the 

 or 

 soft keys to scroll through 

the types and then press the 

  

key to accept the desired type. To 

change the setting, highlight the 

Enter Settings

 option and press the 

 

key.  

Press/Kfact

 allows for calculating flow rate from diffusers or flow 

stations with pressure taps using the instruments pressure ports and 
Kfactors. The Kfactors are obtained from the diffuser or flow station 
manufacturer. For more information, refer to Application Note TSI-114. 

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Summary of Contents for DP-CALC 5825

Page 1: ...DP CALC MICROMANOMETER MODEL 5825 OPERATION AND SERVICE MANUAL P N 1980568 REVISION F FEBRUARY 2016 www GlobalTestSupply com uality Products Online at sales GlobalTestSupp ...

Page 2: ...www GlobalTestSupply com uality Products Online at sales GlobalTestSupp ...

Page 3: ...her than a factory authorized service center with the one exception where requirements set forth in the manual allow an operator to replace consumables or perform recommended cleaning g This warranty is VOID if the product has been misused neglected subjected to accidental or intentional damage or is not properly installed maintained or cleaned according to the requirements of the manual Unless sp...

Page 4: ... s factory shall be at Buyer s risk of loss and will be returned if at all at Seller s risk of loss Buyer and all users are deemed to have accepted this LIMITATION OF WARRANTY AND LIABILITY which contains the complete and exclusive limited warranty of Seller This LIMITATION OF WARRANTY AND LIABILITY may not be amended modified or its terms waived except by writing signed by an Officer of Seller Se...

Page 5: ...R 3 OPERATION 5 Keypad Functions 5 Common Terms 5 Menus 6 DISPLAY SETUP 6 PRESSURE ZERO 6 SETTINGS 6 FLOW SET UP 6 ACTUAL STANDARD SETUP 7 DATA LOGGING 7 Measurements 7 Log Mode Log Settings 7 Delete Data 8 Memory 8 LogDat2TM Downloading Software 8 CHAPTER 4 MAINTENANCE 9 Recalibration 9 Cases 9 Storage 9 CHAPTER 5 TROUBLESHOOTING 11 APPENDIX A SPECIFICATIONS 13 www GlobalTestSupply com uality Pro...

Page 6: ...ntainer Check the individual parts against the list of components below If anything is missing or damaged notify TSI immediately 1 Carrying case 2 Instrument 3 Pressure tubing 4 Static pressure tip 5 USB cable 6 CD ROM with downloading software www GlobalTestSupply com uality Products Online at sales GlobalTestSupp ...

Page 7: ...ery acid leakage Using the Optional AC Adapter When using the AC adapter the batteries if installed will be bypassed Be sure to provide the correct voltage and frequency which is marked on the back of the AC adapter The AC adapter will not recharge the batteries Connecting to a Computer Use the Computer Interface USB Cable to connect the instrument to a computer For information on how to download ...

Page 8: ...llowing is a brief explanation of the meanings of those terms Sample Consists of all of the measurement parameters stored at the same time Test ID A group of samples The statistics average minimum maximum and count are calculated for each test ID The maximum number of test IDs is 100 Time Constant The time constant is an averaging period It is used to dampen the display If you are experiencing flu...

Page 9: ...t will indicate if the pressure zero was successful SETTINGS Settings menu is where you can set the general settings These include Language Beeper Select Units Time Constant Contrast Set Time Set Date Time Format Date Format Number Format Backlight and Auto Off Use the or soft keys to scroll through the settings for each option and use the key to accept settings FLOW SET UP In Flow Setup mode ther...

Page 10: ...Temp range is from 40 to 1832 F 40 to 1000 C DATA LOGGING Measurements Measurements to be logged are independent of measurements on the display and must therefore be selected under DATA LOGGING Measurements When set to ON measurement will be logged to memory When set to DISPLAY measurement will be logged to memory if it is visible on the main running screen When set to OFF measurement will not be ...

Page 11: ...which is designed to provide you with maximum flexibility and power To install this software on your computer follow the instructions on the label of the LogDat2 CD ROM To download data from the Model 5825 connect the supplied computer interface USB cable to the Model 5825 and to a computer USB port Then run the LogDat2 downloading software Within the LogDat2 software either select the tests to be...

Page 12: ...tments are intended to make minor changes in calibration to match a user s calibration standards The field adjustment is NOT intended as a complete calibration capability For complete multiple point calibration and certification the instrument must be returned to the factory Cases If the instrument case or storage case needs cleaning wipe it off with a soft cloth and isopropyl alcohol or a mild de...

Page 13: ...es or plug in AC adapter Dirty battery contacts Clean the battery contacts Reading fluctuates unstable Fluctuating flow Reposition probe in less turbulent flow or use longer time constant No response to keypad Keypad locked out Unlock keypad by pressing keys simultaneously Instrument Error message appears Memory is full Download data if desired then DELETE ALL memory Fault in instrument Factory se...

Page 14: ...ow Rate Range Actual range is a function of actual velocity pressure duct size and K factor Instrument Temperature Range Operating 40 to 113 F 5 to 45 C Storage 4 to 140 F 20 to 60 C Instrument Operating Conditions Altitude up to 4000 meters Relative humidity up to 80 RH non condensing Pollution degree 1 in accordance with IEC 664 Transient over voltage category II Data Storage Capabilities Range ...

Page 15: ...psi 190 in H2O 360 mmHg 48 kPa 2 Pressure velocity measurements are not recommended below 1 000 ft min 5 m s and are best suited to velocities over 2000 ft min Range can vary depending on barometric pressure 3 Accuracy is a function of converting pressure to velocity Conversion accuracy improves when actual pressure values increase www GlobalTestSupply com uality Products Online at sales GlobalTes...

Reviews: