Chapter 4: Menu Setup and Navigation
39
ROUND DUCT MEAS
Move: 0.3 in
597 ft
2
/min
0:00
SAVE?
Test 001
Sample 1
Velocity or
volume flow
based on
Primary
selection in
Display Setup
Sample
measurement
countdown
Test ID Name
and Sample
To input round or rectangular duct dimensions, refer to the
Flow Setup
section of this manual.
The instrument operation can be configured three different ways depending on what is selected as the
LogMode/DisplayMode selection found in the data Logging menu:
If LogMode/DisplayMode is set to Manual/Single:
Meter will display
READY
o
Press
READ
to initiate measurement
o
Sample countdown (based on the Time Constant setting) will be displayed
When Sample countdown is complete:
o
Press
SAVE
to store the measurement sample
o
Press
ESC
to discard and repeat measurement
When Sample is saved, meter will prompt user to move probe to the next sample point
If LogMode/DisplayMode is set to Manual/RunAvg:
Meter will continuously display a reading
User can press
SAVE
at any time
o
Meter will store sample and prompt user to move probe to the next sample point
If LogMode/DisplayMode is set to AutoSave/RunAvg:
Meter will continuously display a reading
User can press
SAVE
at any time
o
Sample countdown (based on the Sample Time) will appear
o
When countdown is completed, measurement will be stored to memory and user will
be prompted to move probe to next sample point.
At anytime during the duct traverse, user can press
STATS
to display statistics of current traverse
(Test ID).
C A U T I O N
Do
not
exit the application while in the middle of the traverse. You will be unable
to return and complete the remaining test points. The traverse will need to be
repeated.