Chapter 4: Menu Setup and Navigation
25
Note
Press/Kfact allows for calculating flow rate from diffusers or flow stations with pressure taps using
the instruments pressure ports and Kfactors. The Kfactors are obtained from the diffuser or flow
station manufacturer. For more information, refer to
Application Note TSI-114
.
Actual/Standard Setup
Choose
Actual/Standard
measurements and parameters in the Actual/Standard Setup menu. The
instrument measures the actual barometric pressure using an internal sensor. The temperature source can
be entered manually or taken from a probe that measures temperature (plug in probe).
MENU
Pressure Tool
Display Setup
Flow Setup
Actual/Std Setup
Settings
Data Logging
Bluetooth Functions
Applications
Cf Selection
Calibration
ACTUAL/STD SETUP
Setting
Standard
Temp Source
Entered
PREVIOUS
NEXT
SETTING
Standard
Actual
TEMP SOURCE
Entered Temp
70.0
F
Probe
The pressure based probes (pitot tube, AF probe and Velocity Matrix) need a valid temperature to
perform the standard or actual velocity or volume flow corrections. This is accomplished in the
Actual/Std Setup
menu. If no probe capable of measuring temperature (plug in probe) is connected,
the
Temp Source
must be set to
Entered
. The air temperature must then be manually inputted using
the
Entered Temp
setting. If the
Temp Source
is set to Probe, and no probe is connected,
dashes (------) will appear on the display.
For the Diffuser Flow tool (Flow from Pressure and K-factor), temperature and barometric pressure are
not used for calculating flow. Therefore, a set temperature is not required for this tool.