27
7-9. Read all channel Disable/Enable status
Command
ID 46 22 00 (CRC)
Syntax
Description
ID
Address of setting module 1~247
46
Function Code
22
Read all channel disable/enable status
00
Reserved code
Response
ID 46 22
HL
00 (CRC)
ID 46 22 ……Module command Line
HL
=Channel 0~F enable/disable status
00 : Reserved code
ID C6 00 (CRC)
ID C6 (CRC) C6:Error function code 00 : Reserved code
Example:
Send command :
”
01 46 22 00”…..Data Channel,
Response:”
01 46 22 0F 00”…Channel 0~3 is enable, Channel 4~7 is disable,
Error Response: “01 C6 00 ”……Error code.
7-10. Perform Spam Calibration
Command
ID 46 25 XX 00 (CRC)
Syntax
Description
ID
Address of setting module 1~247
46
Function Code
25
Spam calibration enable
XX
XX=00 Disable XX=01 Enable
00
Reserved code
Response
ID 46 25
00 00
(
CRC)
ID 46 25 00 ……Module command Line
00 : Reserved code
ID C6 00 (CRC)
ID C6 (CRC) C6:Error function code00 : Reserved code
Example:
Send command ”01 46 25 01 00”,
Response:” 01 46 25 00”…Set up enable,
Error Response: “01 C6 00”……Error code.