14
Then send command:”#01”……Read channel 0~7,
Response:” +02.130+07.512-01.765-02.986
+00.000+00.000+00.000+00.000,
From channel 4~7 is disable.
5-14. Read analog input channel enable/disable status
Command
$ID7(CHK)(cr)
Syntax
Description
$
First leading code
ID
Address of setting module from 00~FF(HEX)
7
Read analog input channel enable/disable status
CHK
Checksum
(cr)
Carriage return
Response
!ID
HL
(CHK)(cr)
H: Channel 4~7 L: Channel 0~3
0:Channel disable 1:Channel Enable
?ID(CHK)(cr)
Command Invalid
Example:
Send command:”$017”,
Response: “!01
0F
”
Channel 4~7 disable, Channel 0~3 enable.
5-15. Set up the calibration Enable/Disable
Command
~IDEV(CHK)(cr)
Syntax
Description
$
First leading code
ID
Address of setting module from 00~FF(HEX)
E
V
V
=0 Disable
V
=1 Enable
CHK
Checksum
(cr)
Carriage return
Response
!ID(CHK)(cr)
Command valid
?ID(CHK)(cr)
Return not enable calibration before calibration command
Example:
Send command:”~01E1”,
Response: “!01”……
Enable calibration.
*Refer to paragraph 4 Function description before calibration.