background image

Installation instructions

Aventa compact plus AU

Summary of Contents for Aventa compact plus AU

Page 1: ...Installation instructions Aventa compact plus AU...

Page 2: ...8 Aventa compact plus AU Symbols used The device must only be installed and repaired by an expert Symbol indicates a possible hazard Note containing information and tips Technical data Determined on...

Page 3: ...with mounting 2 screws 2 9 x 16 for mounting 2 AAA batteries 1 set of operating and installation instructions 1 installation template 3 Wago clamps 1 control panel cable Air distributor to be ordered...

Page 4: ...Truma recommends clearance of 50 mm so that the exhaust air can blow out freely 5 0 560 50 50 7 8 5 2 0 2 0 Fig 8 The clearance around the air distributor must allow the air to blow out without obstr...

Page 5: ...e upper and lower sur faces of the roof The insulation may have to be removed When the skylight with safety ventilation is replaced by the air conditioning system it must be ensured that the safety ve...

Page 6: ...hick M6 screws length roof thickness 30 mm with tensile strength of 8 8 must be used The screws must be secured with low strength screw sealant e g Loctite 1 8 Nm Fig 18 Preparation for power cable co...

Page 7: ...50 mm 1 2 3 Fig 19 Securing the air distributor Connect the cable from the air distributor and the control panel cable to the control unit Fig 20 Screw air distributor arrow in direction of travel to...

Page 8: ...has been routed to the connect ing point All cables must be secured with clamps An insulating device for providing all pole insulation from the mains with contact clearance of at least 3 5 mm must be...

Page 9: ......

Page 10: ......

Page 11: ......

Page 12: ...07 2018 E Mail service leisure tec com au In Australia always notify the Service Australia if problems are encountered in other countries the relevant service partners should be contacted www truma co...

Reviews: