background image

............ www.truemfg.com ............

True Food Service Equipment, Inc.

26

26

INSTALLATION / OPERATION INSTRUCTIONS

IF THE COMPRESSOR WILL NOT 

RUN

1. If there is no voltage at the compressor 

terminals, follow the wiring diagram 

and check back from compressor to the 

power supply to find where the circuit is 

interrupted.

2. If power is available at the compressor 

terminals, and the compressor does not 

run, check the voltage at the compressor 

terminals while attempting to start the 

compressor.

If voltage at the compressor terminals is 

below 90% of the nameplate voltage, it 

is possible the motor may not develop 

sufficient torque to start. Check to 

determine if wire sizes are adequate, 

electrical connections are loose, the 

circuit is overloaded, or if the power 

supply is inadequate.

3. On single phase compressors, 

a defective capacitor or relay may 

prevent the compressor starting. If the 

compressor attempts to start but is 

unable to do so, or if there is a humming 

sound, check the relay to see if the relay 

contacts are damaged or fused. The relay 

points should be closed during the initial 

starting cycle, but should open as the 

compressor comes up to speed.

Remove the wires from the starting 

relay and capacitors. Use a high voltage 

ohmmeter to check for continuity 

throughout the relay coil. Replace 

the relay if there is not continuity. 

Use an ohmmeter to check across the 

relay contacts. Potential relay contacts 

are normally closed when the relay is 

not energized, current relay contacts 

are normally open. If either gives an 

incorrect reading, replace the relay.

Any capacitor found to be bulging, 

leaking, or damaged should be replaced.

Make sure capacitors are discharged 

before checking. Check for continuity 

between each capacitor terminal and the 

case. Continuity indicates a short, and 

the capacitor should be replaced. 

Substitute a “known to be good” start 

capacitor if available. If compressor then 

starts and runs properly, replace the 

original start capacitor.

If a capacitor tester is not available, an 

ohmmeter may be used to check run 

and start capacitors for shorts or open 

circuits. Use an ohmmeter set to its 

highest resistance scale, and connect 

prods to capacitor terminals.

 

a) With a good capacitor, the  

indicator should first move zero, and 

then gradually increase to infinity.

 

b) If there is no movement of 

the ohmmeter indicator, an open circuit 

is indicated.

 

c) If the ohmmeter indicator 

moves to zero, and remains there or on a 

low resistance reading, a short circuit is 

indicated. Defective capacitors should be 

replaced.

4. If the correct voltage is available 

at the compressor terminals, and no 

current is drawn, remove all wires from 

the terminals and check for continuity 

through the motor windings. On single 

phase motor compressors, check for 

continuity from terminals C to R, and 

C to S. On compressors with line break 

inherent protectors, an open overload 

protector can cause a lack of continuity. 

If the compressor is warm, wait one hour 

for the compressor to cool and recheck. 

If continuity cannot be established 

through all motor windings, the 

compressor should be replaced.

Check the motor for ground by means of 

a continuity check between the common 

terminal and the compressor shell. If 

there is a ground, replace the compressor.

5. If the compressor has an external 

protector, check for continuity through 

the protector or protectors. All external 

inherent protectors on compressors can 

be replaced in the field.

IF THE MOTOR COMPRESSOR 

STARTS BUT TRIPS 

REPEATEDLY ON THE 

OVERLOAD PROTECTOR

1. Check the compressor suction and 

discharge pressures while the compressor 

is operating. Be sure the pressures are 

within the limitations of the compressor. 

If pressures are excessive it may be 

necessary to clean the condenser, purge 

air from the system, replace crankcase 

pressure regulating valve.

An excessively low suction pressure may 

indicate a loss of charge.

On units with no service gauge parts 

where pressures can be checked, check 

condenser to be sure it is clean and fan 

is running. Excessive temperatures on 

suction and discharge line may also 

indicate abnormal operating conditions.

2. Check the line voltage at the motor 

terminals while the compressor is 

operating. The voltage should be within 

10% of the nameplate voltage rating. If 

outside those limits, the voltage supply 

must be brought within the proper 

range, or a motor compressor with 

different electrical characteristics must be 

used. 

3. Check the amperage drawn while the 

compressor is operating. Under normal 

operating conditions, the amperage 

drawn will seldom exceed 110% of the 

nameplate amperage. High amperage 

can be caused by low damage, defective 

running capacitors, or a defective starting 

relay.

Summary of Contents for GDM-23

Page 1: ...s Only 25 Field Troubleshooting Freezer Units Only 26 27 Light Cover Install for GDM 10F GDM 12F 28 Maintenance Care Cleaning Cleaning Condenser Coil 29 30 Stainless Steel Equipment Care Cleaning 31 3...

Page 2: ...www truemfg com True Food Service Equipment Inc...

Page 3: ...sonnel Do not puncture refrigerant tubing Caution Risk of fire or explosion Flammable refrigerant used Consult repair manual owner s guide before attempting to service this product All safety precauti...

Page 4: ...www truemfg com True Food Service Equipment Inc SAFETY INFORMATION 2 2...

Page 5: ...recycling appliance please make sure that the refrigerants are handled according to local and national codes requirements and regulations Refrigerant Disposal Your old refrigerator may have a cooling...

Page 6: ...l power cords that have become frayed or otherwise damaged Do not use a cord that shows cracks or abrasion damage along its length or at either end When removing the refrigerator away from the wall be...

Page 7: ...e unit A Remove the outer packaging cardboard and bubbles or styrofoam corners and clear plastic Inspect for concealed damage Again immediately file a claim with the freight carrier if there is damage...

Page 8: ...eveling C The cooler should be leveled front to back and side to side with a level D Ensure that the drain hose or hoses are positioned in the pan E Free plug and cord from inside the lower rear of th...

Page 9: ...d stem of the castor See image 2 C If more than one shim is used turn the slot at a 90 angle so they are not in line D Turn the bearing race clockwise to tighten and secure the castor by tightening th...

Page 10: ...s illustrated and locked down with the hand brakes WARNING Unit may tip forward if procedure F is not strictly followed G Units final location should be adequately ventilated Conditions where heat exc...

Page 11: ...s can not be removed unless placed in specific locations stated in these instructions STEP 2 Two Door Units Slide the front door so it is centered on the cabinet The door can not be removed unless it...

Page 12: ...8 6 6 6 6 5 4 4 3 35 10 10 8 6 6 6 5 5 4 4 3 2 40 10 8 8 6 6 5 5 4 4 3 2 2 45 10 8 6 6 6 5 4 4 3 3 2 1 50 10 8 6 6 5 4 4 3 3 2 1 1 Wire Gauge for 2 Voltage Drop in Supply Circuits 230 Volt Distance I...

Page 13: ...e level side to side and front to back Place a carpenter s level in the interior floor in four places A Position level in the inside floor of the unit near the doors Level should be parallel to cabine...

Page 14: ...iring and installation are correct and no shipping damage has occurred Remember our factory warranty does not cover product loss REPLACEMENT PARTS TRUE maintains a record of the cabinet serial number...

Page 15: ...e Equipment Inc 13 13 INSTALLATION OPERATION INSTRUCTIONS IF YOUR CABINET IS BUILT WITH THIS TEMPERATURE CONTROL PLEASE SEE THE FOLLOWING INSTRUCTIONS On GDM Freezers the LAE Electronic Control is loc...

Page 16: ...Set Point temperature that will start the compressor Example If the Set Point is 9 F 23 C and the Differential is 10 F 5 C Set Point 9 F 10 Differential 1 F Or Set Point 23 C 5 Differential 18 C The c...

Page 17: ...hange the lock settings If no appears the controller is unlocked If yes appears the controller is locked See images 3 and 4 C Once the lock setting has been set correctly release the info button Wait...

Page 18: ...Manual Activation button B To control interior sign lights by the interior door switch depress the rocker switch to the ON position Light Switch is located on inside top right of the ceiling ON Posit...

Page 19: ...ing LAE Control Icons May need to unlock control WHY THE SET POINT IS THE TEMPERATURE AT WHICH THE COMPRESSOR WILL SHUT OFF Please note that the set point IS NOT the cabinet holding temperature HOW A...

Page 20: ...d release the Manual Defrost button until dEF appears B REAL TIME CLOCK RTC If controller is preprogrammed for RTC press the and hold the Manual Defrost button for 5 seconds until dh1 appears Release...

Page 21: ...To see the set point press and hold the info button and the stand by button at the same time ScL will appear See image 1 B Push the up button until dFt appears See image 2 C Press and hold the info b...

Page 22: ...www truemfg com True Food Service Equipment Inc SAFETY INFORMATION 20 20 DISPLAY...

Page 23: ...228 DDY OS2 X 1 8 75 167 1 925 FID T3 80 176 1 669 FDD X 32 1 8 OS3 X 1 8 85 185 1 452 FTO TLD 90 194 1 268 FCM SIM 95 203 1 145 FDT X 1 8 ADR 100 212 0 974 FDH X 1 8 105 221 0 858 FT1 110 230 0 758...

Page 24: ...essary to warm up the set points To make the adjustment insert the appropriate tool in each adjustment screw and turn 1 4 of a revolution clockwise to the right This procedure will adjust both the cut...

Page 25: ...helf clips before installing the shelves 2 Start at the bottom in terms of shelf installation and work your way up 3 Always lay the back of each shelf down on the rear clips before the front WARNING D...

Page 26: ...rganizer until it snaps in place on top of shelf image 3 Tabs grip between shelf wire supports image 3a Step 4 Line up second TrueFlex organizer against the side of the first one and press into place...

Page 27: ...freezer contains a defrost system that is temperature terminated however the time clock has been designed with a time termination back up so that the defrost period will not exceed thirty minutes Whil...

Page 28: ...nd then gradually increase to infinity b If there is no movement of the ohmmeter indicator an open circuit is indicated c If the ohmmeter indicator moves to zero and remains there or on a low resistan...

Page 29: ...te rating may indicate a broken suction reed or broken connecting rod in the compressor IF THE MOTOR COMPRESSOR STARTS BUT TRIPS REPEATEDLY ON THE OVERLOAD PROTECTOR 1 Defrost Time Clock A Check timer...

Page 30: ...r into the bottom groove of the rubber gasket and rotate upwards while working the edges into the rest of the rectangular groove See Images 2 3 slide fingers underneath top edges of rubber gasket and...

Page 31: ...___________ STEP 5 _____________ Lift cardboard cover above fan at plastic plugs and carefully clean condenser coil and fan blades ____________ STEP 6 _____________ INDOOR LOCATION After brushing cond...

Page 32: ...nit You must remove the cabinet grill to expose the Condenser The Condenser looks like a group of vertical fins You need to be able to see through the condenser for the unit to function at maximum cap...

Page 33: ...cannot see the grain 3 Use alkaline alkaline chlorinated or non chloride containing cleaners While many traditional cleaners are loaded with chlorides the industry is providing an ever increasing cho...

Page 34: ...oshine applied provides barrier film for fingerprints and smears C Cameo Talc Zud First Impression is applied by rubbing in the direction of the polished lines for stubborn stains and discoloring D Ea...

Page 35: ...er must also be the same capacity as the drier being replaced 3 Micron level vacuums must be achieved to insure low moisture levels in the system 500 microns or lower must be obtained All claims for l...

Reviews: