![True Manufacturing Company 922341 Installation Manual Download Page 9](http://html1.mh-extra.com/html/true-manufacturing-company/922341/922341_installation-manual_1175468009.webp)
............ www.truemfg.com ............
True Food Service Equipment, Inc.
7
7
INSTALLATION / OPERATION INSTRUCTIONS
CONDUCTORS AND CIRCUITS
Wire Gauge for 2% Voltage Drop in Supply Circuits.
115 Volt
Distance In Feet To Center of Load
Amps 20 30 40 50 60 70 80 90 100 120 140 160
2
14 14 14 14 14 14 14 14 14 14 14 14
3
14 14 14 14 14 14 14 14 14 14 14 12
4
14 14 14 14 14 14 14 14 14 12 12 12
5
14 14 14 14 14 14 14 12 12 12 10 10
6
14 14 14 14 14 14 12 12 12 10 10 10
7
14
14
14
14
14
12
12
12
10
10
10
8
8
14
14
14
14
12
12
12
10
10
10
8
8
9
14
14
14
12
12
12
10
10
10
8
8
8
10
14
14
14
12
12
10
10
10
10
8
8
8
12
14
14
12
12
10
10
10
8
8
8
8
6
14
14
14
12
10
10
10
8
8
8
6
6
6
16
14
12
12
10
10
8
8
8
8
6
6
6
18
14
12
10
10
8
8
8
8
8
8
8
5
20
14
12
10
10
8
8
8
6
6
6
5
5
25
12
10
10
8
8
6
6
6
6
5
4
4
30
12
10
8
8
6
6
6
6
5
4
4
3
35
10
10
8
6
6
6
5
5
4
4
3
2
40
10
8
8
6
6
5
5
4
4
3
2
2
45
10
8
6
6
6
5
4
4
3
3
2
1
50
10
8
6
6
5
4
4
3
3
2
1
1
Wire Gauge for 2% Voltage Drop in Supply Circuits.
230 Volt
Distance In Feet To Center of Load
Amps 20 30 40 50 60 70 80 90 100 120 140 160
5 14 14 14 14 14 14 14 14 14 14 14 14
6 14 14 14 14 14 14 14 14 14 14 14 12
7
14
14
14
14
14
14
14
14
14
14
12
12
8
14
14
14
14
14
14
14
14
14
12
12
12
9 14 14 14 14 14 14 14 14 12 12 12 10
10 14 14 14 14 14 14 14 12 12 12 10 10
12 14 14 14 14 14 14 12 12 12 10 10 10
14
14
14
14
14
14
12
12
12
10
10
10
8
16
14
14
14
14
12
12
12
10
10
10
8
8
18
14
14
14
12
12
12
10
10
10
8
8
8
20
14
14
14
12
10
10
10
10
10
8
8
8
25
14
14
12
12
10
10
10
10
8
8
6
6
30
14
12
12
10
10
10
8
8
8
6
6
6
35
14
12
10
10
10
8
8
8
8
6
6
5
40
14
12
10
10
8
8
8
6
6
6
5
5
50
12
10
10
8
6
6
6
6
6
5
4
4
60
12
10
8
6
6
6
6
6
5
4
4
3
70
10
10
8
6
6
6
5
5
4
4
2
2
80
10
8
8
6
6
5
5
4
4
3
2
2
90
10
8
6
6
5
5
4
4
3
3
1
1
100
10
8
6
6
5
4
4
3
3
2
1
1