The installation of air terminal devices in humid
rooms, areas with potentially explosive atmos-
pheres or rooms with dust-laden or aggressive air
has to be assessed for each individual case.

Transport and storage

Delivery check

Upon delivery, carefully remove the packaging and
check the unit for transport damage and complete-
ness. In case of any damage or an incomplete ship-
ment, contact the shipping company and your sup-
plier immediately. Put the product back into its
packaging after the delivery check to protect it from
dust and contamination.

 Fixing and installation material

Fixing and installation material is not part of the
supply package (unless stated otherwise), but
has to be provided by others; it has to be suitable
for the installation situation.

Transport on site

 CAUTION!

Danger of injury from sharp edges, sharp cor-
ners and thin sheet metal parts!

Sharp edges, sharp corners and thin sheet metal
parts may cause cuts or grazes.

Be careful when carrying out any work.

Wear protective gloves, safety shoes and a
hard hat.

If the device has to be moved:

Be careful when unloading or moving the
product, and pay attention to the symbols and
information on the packaging.

If possible, take the device in its transport
packaging up to the installation location.

Use only lifting and transport gear designed for
the required load.

Always secure the load against tipping and
falling.

Do not move bulky items just by yourself. Get
help to prevent injuries and damage.

Storage

Please note:

Store the unit only in its original packaging

Protect the unit from the effects of weather

Protect the unit from humidity, dust and con-
tamination

Storage temperature: –10 to 50 °C

Relative humidity: 95 % max., non-condensing

Packaging

Properly dispose of packaging material.

Transport and storage

 

Air terminal devices Slot diffusers, Type VSD...

3

Summary of Contents for VSD15

Page 1: ...tional equipment This manual describes the following product types VSD15 VSD35 VSD50 VSD35 Varyset VSD50 1 LT VSD35 3 AZ Installation manual GB en Air terminal devices Slot diffusers Type VSD TROX Gmb...

Page 2: ...uals Unauthorised modifications The actual scope of delivery may differ from the information in this manual for special constructions additional order options or as a result of recent technical change...

Page 3: ...harp edges sharp cor ners and thin sheet metal parts Sharp edges sharp corners and thin sheet metal parts may cause cuts or grazes Be careful when carrying out any work Wear protective gloves safety s...

Page 4: ...n accessible for cleaning even after installation Installation and sealing material which the manufacturer provides is usually supplied in an extra bag Before you install the device take suitable prec...

Page 5: ...such as ropes cables or metal hangers Fig 2 1 to the ceiling 2 Use all of the available suspension points on the plenum box Slot diffusers linear run Fig 3 Linking slot diffusers 3 The supplied connec...

Page 6: ...eal End seal tubular Continuous linear runs require an end seal on each end to ensure that no air leaks End seals can be either factory fitted or fitted by others Single diffusers require end seals on...

Page 7: ...ace of slot diffusers with concealed screw fixing variant AS or DS can be fixed to the plenum box after the false ceiling has been completed Fig 7 Diffuser face with concealed screw fixing Installatio...

Page 8: ...e Ceiling Suspended ceiling VSD50 1 LT Duct Installation opening Nominal length l mm h mm 550 560 58 1175 1185 VSD35 3 AZ For wall and bulkhead installation Preferably for rooms with a clear height up...

Page 9: ...ed to the ducting For commissioning see also VDI 6022 part 1 Hy giene requirements for ventilation and air condi tioning systems and units Volume flow rate balancing When several diffusers are connect...

Page 10: ...rol elements Alternating horizontal air discharge Alternating air control elements every second element different One way horizontal air discharge to the left One way horizontal air discharge to the r...

Page 11: ...ng intervals given in the VDI 6022 standard apply Clean surfaces with a damp cloth Use only common household cleaners do not use any aggressive cleaning agents Cleaning agents that contain chlorine mu...