3
Structure and functional description
3.1 Product overview types LVC, TVR, TVJ, TVT, TZ-Silenzio, TA-Silenzio, TVZ, TVA
Fig. 1: Easy controller mounted on the control unit e.g. TVR
1
Easy controller
2
Measuring hoses
3
VAV terminal unit
4
Sensor tubes of the control unit
5
Wire clamping bracket
6
Scale sticker for setting q
vmin
/q
vmax
(V
min
/ V
max
)
7
Terminals
8
'Test' push button
9
LED for displaying the operating states, see table
10
q
vmin
potentiometer (V
min
)
11
q
vmax
potentiometer (V
max
)
12
Axle mounting (positive connection or clamping
device)
13
Travel stops
14
Protective cap
15
Tube connection transducer
–
Adjustments sticker on VAV terminal unit (not pic-
tured)
16
Service socket, not functional on Easy
Detection of operating states (LED)
LED
Operating status
ON
Target volume flow rate reached
Off
Test push button pressed
No supply voltage
Easy controller faulty
Flashes (slowly 0.5 Hz)
Actual value
≠
setpoint value, controller tries to control to the setpoint
value
Test operation started
Synchronisation process active
Flashes (rapidly 2.5 Hz)
Direction of rotation change confirmation
direction of rotation’ on page 25
Then slowly flashing until the synchronisation process is completed.
Structure and functional description
Product overview types LVC, TVR, TVJ, TVT, TZ-Si...
Easy control component for VAV terminal units
10