For adaptation, the actuator moves to the
end positions and then automatically
switches to control mode.
Functional test
6.
To complete commissioning, perform a func-
tional test of the controller using the Easy-
Connect software, taking into account the
project specifications for the required oper-
ating modes.
Compare the volume flow rate setpoint value
for each operating mode with the actual
value and document the results. Check if
alarms are emitted and signaled with the
functional test.
Commissioning
EASYLAB controller Serie TCU3
24