6.3.11
Humidifier
Setting up the humidifier
Personnel:
HVAC technician
Protective equipment:
Protective clothing
Industrial safety helmet
Hearing protection
Protective gloves
Safety shoes
The position of the droplet eliminator and demister
cassettes may have changed due to vibrations
during transport.
If there are gaps between the cassettes, mist from
the humidifier module could get into the unit and
accumulate to water.
The droplet eliminator cassettes can only be
checked upstream of the humidifier, and the demister
cassettes downstream of the humidifier. It may be
necessary to disconnect ducts to get access to the
cassettes.
Fig. 67: Droplet eliminator cassettes
1.
Check the position of each droplet eliminator cas-
sette. If there is a gap between any two cassettes,
adjust the position of the cassettes.
Fig. 68: Demister cassettes
2.
Check the position of each demister cassette. If
there is a gap between any two cassettes, adjust
the position of the cassettes.
NOTICE!
Be sure to comply with the humidifier manufac-
turer's instructions for commissioning.
3.
Check water connections and water pipes
installed in the air handling unit for leaks. Re-
tighten the screw connections in case of leaks.
ð
The humidifier is now ready for use.
6.3.12
Electrical system
Personnel:
Skilled qualified electrician
Protective equipment:
Protective clothing
Hearing protection
Industrial safety helmet
Protective gloves
Safety shoes
Before commissioning, the electrical system has to be
tested according to IEC 60364-6 (VDE 0100-600). As
part of this test, all contacts have to be checked for cor-
rect seating. This applies in particular to motor terminal
blocks, fuses, local isolators etc.
6.4 Starting the air handling unit
6.4.1 Before you start the AHU
Before you switch on the air handling unit, make sure
that the following requirements have been met:
Initial commissioning
Starting the air handling unit > Before you start the AHU
Air handling unit X-CUBE
64