Installation
General installation information
Fig. 4: Positioning
Please note:
All modules that should communicate via radio
have to be installed in the same duct system,
i.e. either in the supply air duct or in the extract
air duct.
Place the antenna at least 1 m away from con-
trol dampers, shut-off dampers and measuring
devices.
The distance between the RadioDuct module
and the antenna must not exceed 40 cm.
The distance between the RadioDuct module
and ZMA / ZMO must not exceed 30 m.
Fix the antenna in the middle of the duct wall
(applies to rectangular ducts).
Fig. 5: Position on ducts
Fixing the antenna mounting bracket
Fig. 6: Fixing material (not included in the supply
package)
Fig. 7: Drill a hole
Æ
10 mm
Fig. 8: Use the screws to fix the bracket
Installation