9
K values
Rounded VAV terminal units
Serie
ØD
[mm]
C-Wert
(-> l/s)
LVC 1)
125
–
LVC 1)
160
–
LVC 1)
200
–
LVC 1)
250
–
TVE 1)
125,00
–
TVE 1)
160,00
–
TVE 1)
200,00
–
TVE 1)
250,00
–
TVR
100
6,10
TVR
125
9,97
TVR
140
12,40
TVR
160
16,00
TVR
200
26,06
TVR
250
39,50
TVR
315
65,60
TVR
400
108,18
TVRK
125
8,60
TVRK
160
15,10
TVRK
200
24,30
TVRK
250
38,00
TVRK
315
62,00
TVRK
400
103,00
TVLK
2)
--> 2009
250-0
43,06
TVLK
3)
2009 -->
250-0
38,33
TVLK
250-100
25,00
TVLK
250-110
24,31
TVLK
250-140
21,53
TVLK
250-160
13,33
TVLK
250-180
15,14
TVLK
250-D08
33,89
TVLK
250-D10
24,30
TVLK
250-D16
13,75
TVR-Ex
125
9,97
TVR-Ex
160
16,00
TVR-Ex
200
26,06
TVR-Ex
250
39,50
TVR-Ex
315
65,60
TVR-Ex
400
108,18
1) LVC, TVE: no calculation possible using K value
2) TVLK: with four parallel measuring tubes made
before approx. 2009
3) TVLK: with four crossed measuring tubes made from
approx. 2009 onwards
Rectangular VAV terminal units
C-Wert
(-> l/s)
TVJ
–
200
100
15,17
TVJ
–
300
100
22,75
TVJ
–
400
100
30,34
TVJ
–
500
100
37,92
TVJ
–
600
100
45,50
TVJ
–
200
200
30,34
TVJ
–
300
200
45,50
TVJ
–
400
200
60,67
TVJ
–
500
200
75,84
TVJ
–
600
200
91,01
TVJ
–
700
200
106,17
TVJ
–
800
200
121,34
TVJ
–
300
300
74,51
TVJ
–
400
300
99,35
TVJ
–
500
300
124,19
TVJ
–
600
300
149,03
TVJ
–
700
300
173,86
TVJ
–
800
300
198,70
TVJ
–
900
300
223,54
TVJ
–
1000
300
248,38
TVJ
–
400
400
138,03
TVJ
–
500
400
172,54
TVJ
–
600
400
207,05
TVJ
–
700
400
241,55
TVJ
–
800
400
276,06
TVJ
–
900
400
310,57
TVJ
–
1000
400
345,08
TVJ
–
500
500
200,03
TVJ
–
600
500
240,03
TVJ
–
700
500
280,04
TVJ
–
800
500
320,04
TVJ
–
900
500
360,05
TVJ
–
1000
500
400,06
TVJ
–
600
600
298,05
TVJ
–
700
600
347,73
TVJ
–
800
600
397,40
TVJ
–
900
600
447,08
TVJ
–
1000
600
496,76
TVJ
–
700
700
415,42
TVJ
–
800
700
474,76
TVJ
–
900
700
534,11
TVJ
–
1000
700
593,46
TVJ
–
800
800
552,12
TVJ
–
900
800
621,14
TVJ
–
1000
800
690,16
TVJ
–
900
900
708,17
TVJ
–
1000
900
786,86
TVJ
–
1000
1000
883,56
Serie
ØD
[mm]
B
[mm]
H
[mm]
K values
VAV terminal units VARYCONTROL