Type
Illustration
Description
TVZ
①
Differential pressure sensor
②
Lip seal
③
Inspection access
④
Damper blade
⑤
Integral sound attenuator
⑥
Control components, e.g. Easy controllers
TVA
①
Integral sound attenuator
②
Lip seal
③
Damper blade
④
Differential pressure sensor
⑤
Control components, e.g. Easy controllers
TVM
①
Damper blade – cold air
②
Lip seal
③
Differential pressure sensor – cold air
④
Control components, e.g. compact control-
lers
⑤
Inspection access
⑥
Differential pressure sensor – total air
⑦
Noise insulation
⑧
Damper blade – warm air
Notes for terminal units for duct pressure control
The accessibility of the connections for the differential pressure sensors varies depending on the version of
the VAV terminal unit, and the control components installed.
VAV terminal units intended for duct pressure control require a suitable pressure tapping point in the duct
system to be controlled. In VAV terminal units with control components for duct pressure control, the differen-
tial pressure sensor installed in the VAV terminal unit has no function and is therefore either not accessible or
designed without tubing to the control component.
Product description
VAV terminal unit types > Rectangular VAV terminal units, steel
VAV terminal units VARYCONTROL
13