7
Maintenance and cleaning
Maintenance measures
Job
Interval
daily
as required
4 weeks
6 months
1 year
2 years
Check air inlet and outlet for for-
eign matter and contamination,
clean if necessary
X
Cleaning the outside of the
casing
X
X
Check the inside of the casing
for contamination, clean if nec-
essary
X
X
Check fixing screws
X
Replace HEPA filter
X
X
Replace prefilter
X
X
Test run
X
7.1 Check and change filter
Personnel:
Instructed person
Protective equipment:
Disposable gloves
Dust mask FFP2
Special tool:
Allen key size 10
We recommend only carrying out a filter change outside
the period of use to avoid the risk of infection for other
people.
1.
Switch the unit off,
2.
Disconnect the mains plug!
Remove the mains plug from the socket.
3.
Open the door by removing the cover cap on the
lock and opening the door lock with a size 10 hex-
agon socket key.
Checking prefilter
4.
Pull out the prefilter (lower filter).
Check the filter for damage, contamination,
moisture and odours.
Check the filter chambers for contamination
and clean them with a damp cloth if neces-
sary.
ð
Replace the prefilter if required, or according
to the specified change intervals.
Changing prefilter
5.
Pull the contaminated filter out of the air purifier,
put it into a plastic bag and dispose of it properly,
see notes on disposal
6.
Do not touch or damage the filter packs when
inserting the new filters. Only hold the filter by the
frame to avoid damage to the filter.
Checking HEPA filter
7.
Pull out the HEPA filter (upper filter).
Check the filter for damage, contamination,
moisture and odours.
Check the filter chambers for contamination
and clean them with a damp cloth if neces-
sary.
ð
Replace the filter if required, or according to
the specified change intervals.
Changing HEPA filter
8.
Pull the contaminated filter out of the air purifier,
put it into a plastic bag and dispose of it properly,
see notes on disposal
9.
Do not touch or damage the filter packs when
inserting the new filters. Only hold the filter by the
frame to avoid damage to the filter.
10.
Close the door and put the cover cap back on the
door lock. Switch the unit on again,
Maintenance and cleaning
Check and change filter
TROX AIR PURIFIERS TAP-L