background image

Electrical connection

General safety notes

 DANGER!

Danger of electric shock! Do not touch any live com-

ponents! Electrical equipment carries a dangerous

electrical voltage.

Only skilled qualified electricians are allowed to

work on the electrical system.

Switch off the power supply before working on

any electrical equipment.

For any wiring work, follow the national and local regula-

tions and guidelines for electrical installation.

Equipotential bonding

To prevent ignition sources due to static charges, the

fire damper must be integrated into the equipotential

bonding of the ventilation system.

Construction of equipotential bonding (by others):

Single-wire CU-line 4 mm

2

 with ring cable lug.

Connection options of equipotential bonding:

Fire damper with ExMax/RedMax spring return

actuator

Terminal box at PA terminal

FKRS-EU with ExMax or RedMax spring return

actuator

The ExMax or RedMax spring return actuator has auto-

matic voltage detection 24 V – 240 V AC/DC. The

actuator detects the voltage automatically and does not

have to be adjusted.

Connect the spring return actuator according to the

wiring example.

Several actuators can be connected in parallel as long

as the performance specifications are taken into consid-

eration.

Functional testing requires a switch that interrupts the

voltage supply (by others).

The electrical connection is made in the terminal box.

The factory installed wiring must not be changed.

Attention!

If the voltage has been interrupted with either the switch

(1) or the optional release mechanism (2), the heating

(6) is not active.

Wiring example for ExMax or RedMax spring return

actuator

Fig. 2: Actuator connection, example

1

Switch for opening and closing, to be provided by

others

2

Optional release mechanism, e.g. TROX duct

smoke detector type RM-O-3-D or RM-O-VS-D (out-

side the Ex zone)

3

Indicator light for CLOSED position, to be provided

by others

4

Indicator light for OPEN position, to be provided by

others

5

Terminal for equipotential bonding 4 mm

2

6

Heating

TROXNETCOM AS-i

The fire dampers with spring return actuator and module

AS-EM/C (accessory) form a functional unit ready for

automatic operation.

The module is to be installed and wired outside of the

potentially explosive atmosphere by others

The module transmits the control signals between

the spring return actuator and the controller and

power unit. This allows for controlling the actuator

and monitoring the actuator run time during func-

tional testing.

The 24 V DC supply voltage for the module and the

actuator is transmitted using the AS-i flat cable.

Status display:

Operation

4 inputs

2 outputs

Electrical connection

 

 

Explosion-proof fire damper Type FKRS-EU

8

Summary of Contents for FKRS-EU Series

Page 1: ...Explosion proof fire damper Type FKRS EU Supplementary Operating Manual Read the instructions prior to performing any task according to Declaration of Performance DoP FKRS EU DE 004 GB en...

Page 2: ...original 2021 TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany Germany Phone 49 0 2845 2020 Fax 49 0 2845 202 265 E mail trox de troxgroup de Internet http www troxtechnik com 12 2021 Exp...

Page 3: ...data 6 3 1 FKRS EU with explosion proof spring return actuator 6 3 2 ATEX areas of application 7 4 Electrical connection 8 5 Functional test 10 5 1 FKRS EU with ExMax or RedMax spring return actuator...

Page 4: ...nt statutory regulations This supplementary operating manual is intended for specialist consultants developers and owners of the ventilation systems in which the fire dampers are to be installed This...

Page 5: ...components according to the local electronic waste regulations Correct use The fire damper is used as a shut off device to prevent fire and smoke from spreading through ducting in areas with potentia...

Page 6: ...ght kg Nominal size DN 100 125 150 160 180 200 224 250 280 315 D 99 124 149 159 179 199 223 249 279 314 Weight with spring return actuator 4 8 5 1 5 3 5 5 5 8 6 0 6 2 6 8 7 3 7 9 Spring return actuato...

Page 7: ...ExMax 15 BF TR II 2G Ex h IIC T6 Gb II 2D Ex h IIIC T80 C Db 40 C Ta 40 C 10 m s ExPro TT ExMax 15 BF TR II 2G Ex h IIC T5 Gb II 2D Ex h IIIC T95 C Db 40 C Ta 50 C 10 m s ExPro TT RedMax 15 BF TR II...

Page 8: ...on Functional testing requires a switch that interrupts the voltage supply by others The electrical connection is made in the terminal box The factory installed wiring must not be changed Attention If...

Page 9: ...Wiring example for TROXNETCOM Fig 3 Wiring example for TROXNETCOM 1 Controller 2 AS EM C module 3 FKRS EU 4 Safe area Electrical connection Explosion proof fire damper Type FKRS EU 9...

Page 10: ...2 Damper blade is open Closing opening the fire damper with spring return actuator Fig 5 Thermoelectric release mechanism ExPro TT 1 Push button for functional test Fig 6 Functional test FKRS EU with...

Page 11: ...de will not close To re establish its function connect the power supply Requirement The damper blade is CLOSED 1 Remove the terminal box 1 2 Insert the crank handle 2 into the opening for the spring w...

Page 12: ...Explosion proof fire damper Type FKRS EU 12...

Reviews:

Related manuals for FKRS-EU Series