2.2 Installation of FKR-EU
Fig. 4: FKR-EU with thermal insulation
1b
FKR-EU
2.1
Mortar or gypsum mortar
3.1
Solid wall
6.16
Insulating strips, Armaflex AF / Armaflex Ultima,
around the perimeter, actuator and release
mechanism as well as inspection accesses must
be accessible
6.22
Armaflex tape
9.2
Extension piece or duct
A
Installation side
B
Operating side
Additional requirements
Solid wall
Casing length L = 495 or 550 mm
Install the insulating strips (6.16) on site and close off the joint with Armaflex adhesive or with the Armaflex tape
(6.22) provided.
Depending on the local conditions, insulation for larger wall areas may be required. Insulation provided on site
can be installed up to the insulated dire damper casing instead of using insulating strips.
Install the insulation provided on site, e.g. for the ducting or the extension piece (9.2), without gaps.
Note:
This installation manual supplements the installation and operating manual of the FKR-EU. It shows the installa-
tion of the FKR-EU fire damper with thermal insulation in a solid wall. The installation situation shown is represen-
tative for all installation situations and support structures in accordance with the installation and operating manual
FKR-EU.
Installation
Installation of FKR-EU
Fire damper Type FK-EU ODA and FKR-EU ODA with thermal insulation
6