2
Installation
2.1 Installation of FK-EU
Fig. 3: FK-EU with thermal insulation
1a
FK-EU
2.1
Mortar or gypsum mortar
3.1
Solid wall
6.16
Insulating strips, Armaflex AF / Armaflex Ultima,
around the perimeter, actuator and release
mechanism as well as inspection accesses must
be accessible
A
Installation side
B
Operating side
Additional requirements
Solid wall
Casing length L = 305 or 500 mm
Attach the insulating strips provided (6.16) on site and close off the overlaps with reverse adhesive coating.
Depending on the local conditions, insulation for larger wall areas may be required. Insulation provided on site
can be installed up to the insulated dire damper casing instead of using insulating strips.
Install the insulation provided on site, e.g. for the ducting or the extension piece (9.2), without gaps.
* Mortar (2.1) over the insulation is permitted
Note:
These instructions supplement the installation and operating manual of the FK-EU. They show the installation of
the FK-EU fire damper with thermal insulation in a solid wall. The installation situation shown is representative for
all installation situations and support structures in accordance with the installation and operating manual FK-EU.
Installation
Installation of FK-EU
Fire damper Type FK-EU ODA and FKR-EU ODA with thermal insulation
5