Network number
Enter the network number into the
[Network number]
field.
UDP port
Enter the UDP port to be used for BACnet into the
[UDP port]
field.
The default value is 47808 (or 0xBAC0 as a hexa-
decimal value).
Operating mode
Use this field to enter the operating mode.
Normal
BBMD
Foreign Device (FD)
The default is 'Normal'.
NOTICE!
Using BBMD and Foreign Device (FD) incorrectly
may result in serious network problems (broadcast).
Only use these settings for networks where IT routers
block broadcast messages.
Editing a configuration
1.
Select the
‘Setup’
menu from the menu bar.
2.
Under
‘BACnet’
, on the left, select
‘Network’
.
ð
The
‘Network’
3.
Enter new values or change option fields as
required.
4.
Use
[Save]
to save your entries.
3.5.7.11.1
Editing a device object
Fig. 39: Editing a device object
This menu allows you to enter device-specific BACnet
settings.
Editing device object properties
1.
Select the
‘Setup’
menu from the menu bar.
2.
Under
‘BACnet’
, on the left, select
‘Device’
.
ð
The
‘Device’
3.
Enter new values or change option fields as
required.
4.
Use
[Save]
to save your entries.
3.5.7.11.2
BACnet objects
The 'BACnet objects' page allows you to edit existing
data points.
This includes
Intrinsic reporting
Creating trend logs
Events and alarm notification
Scheduler
Web server settings
Web server navigation > Functions of the Setup menu
Expansion module EM-IP
23