* Data applies to uniform upstream and downstream conditions for the smoke control damper

 

 

No. of blades, cross section and sound reduction index, height 430, 630 mm

B

H n

② ③

200

430 2 0,06 0,09 37

250

430 2 0,08 0,11 36

300

430 2 0,09 0,13 36

350

430 2 0,11 0,15 35

400

430 2 0,12 0,17 34

450

430 2 0,14 0,19 34

500

430 2 0,15 0,22 33

550

430 2 0,17 0,24 33

600

430 2 0,18 0,26 33

650

430 2 0,2 0,28 32

700

430 2 0,22 0,30 32

750

430 2 0,23 0,32 32

800

430 2 0,25 0,34 31

850

430 2 0,26 0,37 31

900

430 2 0,28 0,39 31

950

430 2 0,29 0,41 31

1000

430 2 0,31 0,43 30

1050

430 2 0,32 0,45 30

1100

430 2 0,34 0,47 30

1150

430 2 0,35 0,49 30

1200

430 2 0,37 0,52 30

200

630 3 0,09 0,13 36

250

630 3 0,12 0,16 35

300

630 3 0,14 0,19 34

350

630 3 0,16 0,22 33

400

630 3 0,19 0,25 33

450

630 3 0,21 0,28 32

500

630 3 0,23 0,32 32

550

630 3 0,26 0,35 31

600

630 3 0,28 0,38 31

650

630 3 0,3 0,41 31

700

630 3 0,33 0,44 30

750

630 3 0,35 0,47 30

800

630 3 0,37 0,50 30

850

630 3 0,4 0,54 29

900

630 3 0,42 0,57 29

950

630 3 0,44 0,60 29

1000

630 3 0,47 0,63 29

1050

630 3 0,49 0,66 28

1100

630 3 0,51 0,69 28

1150

630 3 0,54 0,72 28

1200

630 3 0,56 0,76 28

Number of blades: n

 Cross section A

 [m ]

 Cross section A

[m ]

 Sound reduction index R [dB]

 

No. of blades, cross section and sound reduction index, height 830, 1030 mm

Free

2

geo 

2

Summary of Contents for EK-JZ

Page 1: ...l sizes 200 430 1200 2030 mm for smoke gas flow rates up to 87700 m h or 24360 l s at 10 m s Quick and easy installation in or on building structures for smoke and heat exhaust remote control with an...

Page 2: ...combined systems and thus pneumatic volume flow rate balancing via the selection of intermediate positions Complies with the requirements of EN 12101 8 Tested to EN 1366 2 and 1366 10 for fire resist...

Page 3: ...control TROX X smoke exhaust fans from the X FANS subassembly Smoke exhaust fan for roof installation BVDAX BVD Smoke exhaust fan for wall installation BVW BVWAXN Smoke exhaust centrifugal fan BVREH B...

Page 4: ...eliability of the smoke control damper must be tested at least every six months this has to be arranged by the owner of the smoke extract system functional tests must be carried out in compliance with...

Page 5: ...n automatically or manually triggered control signal According to the specified time temperature curve an EK JZ can still fully open or close after 25 minutes MA manual release Similarly position chan...

Page 6: ...30 1050 430 2 0 32 0 45 30 1100 430 2 0 34 0 47 30 1150 430 2 0 35 0 49 30 1200 430 2 0 37 0 52 30 200 630 3 0 09 0 13 36 250 630 3 0 12 0 16 35 300 630 3 0 14 0 19 34 350 630 3 0 16 0 22 33 400 630 3...

Page 7: ...27 200 1030 5 0 16 0 21 34 250 1030 5 0 2 0 26 33 300 1030 5 0 24 0 31 32 350 1030 5 0 28 0 36 31 400 1030 5 0 32 0 41 31 450 1030 5 0 35 0 46 30 500 1030 5 0 39 0 52 30 550 1030 5 0 43 0 57 29 600 10...

Page 8: ...6 1 14 1 48 25 200 1430 7 0 22 0 29 32 250 1430 7 0 28 0 36 31 300 1430 7 0 33 0 43 30 350 1430 7 0 39 0 50 30 400 1430 7 0 44 0 57 29 450 1430 7 0 50 0 64 29 500 1430 7 0 55 0 72 28 550 1430 7 0 61 0...

Page 9: ...30 8 1 52 1 96 24 200 1830 9 0 29 0 37 31 250 1830 9 0 36 0 46 30 300 1830 9 0 43 0 55 29 350 1830 9 0 50 0 64 29 400 1830 9 0 57 0 73 28 450 1830 9 0 64 0 82 28 500 1830 9 0 71 0 92 27 550 1830 9 0 7...

Page 10: ...1 83 2 33 23 1200 2030 10 1 91 2 44 23 B H n Number of blades n Cross section A m Cross section A m Sound reduction index R dB Free 2 geo 2 w Quick sizing tables provide a good overview of the volume...

Page 11: ...and casing airleakage to EN 1751 class C Low sound power level and differential pressure Any airflow direction Manual release is also possible using TROXNETCOM Integration into the central BMS with st...

Page 12: ...tor side Sign 2 defines installation side Example FA Connecting subframe on the operating side crimped wire mesh on the installation sideAny combination is possible 8 Attachments 2 Belimo actuators B2...

Page 13: ...issioning Installation on in concrete or masonry shaft walls Installation in lightweight partition walls Installation in shaft walls that are covered on one side Installation in or on tested fire resi...