background image

TECHNICAL INFORMATION

Function, Technical data, Quick sizing, Specification text, Order code

Smoke control dampers are used in mechanical smoke extract systems.

They are used for extracting smoke gases and for providing additional supply air to one or more fire compartments.

The dampers are made of calcium silicate panels and are opened by an encased actuator; when smoke is detected, the actuator is triggered by a signal

either from a duct smoke detector or from a fire alarm system.

Smoke control dampers have two safe positions: open and closed.

In the case of fire-resistant smoke control dampers for multiple compartments, the safe position is either 'open' or 'closed', depending on the fire site and the

path of the smoke to be extracted.

If the safe position is 'open', the free area must be maintained even in the event of a fire.

The blades of EK-JZ move to the defined safe position upon receiving an automatically or manually triggered control signal. According to the specified time-

temperature curve, an EK-JZ can still fully open or close after 25 minutes (MA, manual release).

Similarly, position changes for modulation applications (C

) and thus pneumatic volume flow rate balancing via the section of intermediate positions of

the damper blade section are possible with the product type EK-JZ.

Regular maintenance of the smoke control damper is required to ensure its functional reliability. 

 

 

Schematic illustration

 Casing

 Blades

 Blade tip seal (special profile seal)

 Side seal

 Travel stop, bottom

 Rating plate

 Actuator

 Cover fixing

 Linkage

 Actuator encasing

 Cover of the actuator encasing (sectional view)

 Handle (to remove the cover)

 Travel stop, top

mod

Nominal sizes W × H

200 × 430 mm – 1200 × 2030 mm

Casing length

250 mm

Volume flow rate range

Up to 24361 l/s or 87700 m³/h

Differential pressure range

Pressure level 2: -1000 – 500 Pa

Operating temperature

-30 to 50 °C; the temperature should not fall below the dew point

Upstream velocity*

≤ 10 m/s with the largest size, > 10 – 15 m/s with smaller sizes; 87700 m³/h max.

Summary of Contents for EK-JZ

Page 1: ...l sizes 200 430 1200 2030 mm for smoke gas flow rates up to 87700 m h or 24360 l s at 10 m s Quick and easy installation in or on building structures for smoke and heat exhaust remote control with an...

Page 2: ...combined systems and thus pneumatic volume flow rate balancing via the selection of intermediate positions Complies with the requirements of EN 12101 8 Tested to EN 1366 2 and 1366 10 for fire resist...

Page 3: ...control TROX X smoke exhaust fans from the X FANS subassembly Smoke exhaust fan for roof installation BVDAX BVD Smoke exhaust fan for wall installation BVW BVWAXN Smoke exhaust centrifugal fan BVREH B...

Page 4: ...eliability of the smoke control damper must be tested at least every six months this has to be arranged by the owner of the smoke extract system functional tests must be carried out in compliance with...

Page 5: ...n automatically or manually triggered control signal According to the specified time temperature curve an EK JZ can still fully open or close after 25 minutes MA manual release Similarly position chan...

Page 6: ...30 1050 430 2 0 32 0 45 30 1100 430 2 0 34 0 47 30 1150 430 2 0 35 0 49 30 1200 430 2 0 37 0 52 30 200 630 3 0 09 0 13 36 250 630 3 0 12 0 16 35 300 630 3 0 14 0 19 34 350 630 3 0 16 0 22 33 400 630 3...

Page 7: ...27 200 1030 5 0 16 0 21 34 250 1030 5 0 2 0 26 33 300 1030 5 0 24 0 31 32 350 1030 5 0 28 0 36 31 400 1030 5 0 32 0 41 31 450 1030 5 0 35 0 46 30 500 1030 5 0 39 0 52 30 550 1030 5 0 43 0 57 29 600 10...

Page 8: ...6 1 14 1 48 25 200 1430 7 0 22 0 29 32 250 1430 7 0 28 0 36 31 300 1430 7 0 33 0 43 30 350 1430 7 0 39 0 50 30 400 1430 7 0 44 0 57 29 450 1430 7 0 50 0 64 29 500 1430 7 0 55 0 72 28 550 1430 7 0 61 0...

Page 9: ...30 8 1 52 1 96 24 200 1830 9 0 29 0 37 31 250 1830 9 0 36 0 46 30 300 1830 9 0 43 0 55 29 350 1830 9 0 50 0 64 29 400 1830 9 0 57 0 73 28 450 1830 9 0 64 0 82 28 500 1830 9 0 71 0 92 27 550 1830 9 0 7...

Page 10: ...1 83 2 33 23 1200 2030 10 1 91 2 44 23 B H n Number of blades n Cross section A m Cross section A m Sound reduction index R dB Free 2 geo 2 w Quick sizing tables provide a good overview of the volume...

Page 11: ...and casing airleakage to EN 1751 class C Low sound power level and differential pressure Any airflow direction Manual release is also possible using TROXNETCOM Integration into the central BMS with st...

Page 12: ...tor side Sign 2 defines installation side Example FA Connecting subframe on the operating side crimped wire mesh on the installation sideAny combination is possible 8 Attachments 2 Belimo actuators B2...

Page 13: ...issioning Installation on in concrete or masonry shaft walls Installation in lightweight partition walls Installation in shaft walls that are covered on one side Installation in or on tested fire resi...

Reviews: