5
Installation
5.1 Installation situations
The table lists the various installation types of EK-JZ smoke control dampers; for details on the performance level
see the declaration of performance.
Installation locations described here may be combined with other installation location characteristics. For example, a
smoke control damper may be installed on a vertical smoke extract duct where a horizontal smoke extract duct
branches off.
Supporting con-
struction
Construction
Installation loca-
tion
Installa-
tion type
Performance
level
Installa-
tion
informa-
tion
Horizontal sheet
steel smoke extract
duct
Sheet steel smoke extract
duct tested according to
EN 1366-9
Operating temperature up to
600 °C
on a horizontal
duct
LE
E
600
120
(v
ed
, i↔o) S
in a horizontal
duct
at the end of a
horizontal duct
on top of a hori-
zontal duct
E
600
120
(h
od
, i↔o) S
Vertical sheet steel
smoke extract duct
(horizontal sheet
steel smoke extract
duct with height
offset)
on a vertical duct
E
600
120
(v
ed
, i↔o) S
in a vertical duct
E
600
120
(h
od
, i↔o) S
at the end of a
vertical duct
Vertical solid
smoke extract
ducts
Operating temperature up to
600 °C
on a vertical duct
E
600
120
(v
ed
, i↔o) S
LE = As specified for the duct
5.2 Safety notes regarding installation
Sharp edges, sharp corners and thin sheet metal
parts
CAUTION!
Danger of injury from sharp edges, sharp cor-
ners and thin sheet metal parts!
Sharp edges, sharp corners and thin sheet metal
parts may cause cuts or grazes.
–
Be careful when carrying out any work.
–
Wear protective gloves, safety shoes and a hard
hat.
5.3 General installation information
NOTICE!
Be careful to not damage the smoke control
damper
–
Protect the smoke control damper from contami-
nation and damage.
–
Cover the flange openings and the actuator (e.g.
with plastic) to protect them from mortar and
dripping water.
Please note:
Install the smoke control damper without torsion
(horizontal/vertical).
Make sure that no loads are imposed on the casing
as this may impair the function of the smoke control
damper.
Smoke control damper and electric actuator must
remain accessible for maintenance.
Installation
General installation information
Smoke control damper EK-JS
16
Summary of Contents for EK-JS
Page 53: ...Decommissioning removal and disposal Smoke control damper EK JS 53...
Page 54: ...11 Flange dimensional drawing Flange dimensional drawing Smoke control damper EK JS 54...
Page 57: ...Smoke control damper EK JS 57...
Page 58: ...Smoke control damper EK JS 58...
Page 59: ...Smoke control damper EK JS 59...