Installing the controller

Personnel:

HVAC technician

Protective equipment:

Industrial safety helmet

Protective gloves

Safety shoes

Before you install the product, take suitable precau-
tions to protect air distribution components from
contamination during installation (VDI 6022). If this
is not possible, at least cover the product or take
other precautions to protect it from contamination.
In this case you have to ensure that the product
cannot be started. Ensure that all components are
clean before you install them. If necessary, clean
them thoroughly. If you have to interrupt the installa-
tion procedure, protect all openings from the
ingress of dust or moisture.

For installation please note:

Fix the product only to load-bearing structural
elements.

Load suspension systems only with the weight
of the product. Adjacent components and con-
necting ducts must be supported separately.

Use only approved and adequately sized fixing
material (fixing material is not included in the
supply package).

For maintenance or adjustment work, the
device must be accessible after installation.

Important:

 If there is a risk that the controller

could be subject to mechanical impact during
operation, protect it accordingly; protection has
to be provided by others.

Be careful to not damage the controller accidentally:

Handle the unit with care.

Lift the unit only by lifting the entire casing.

Never lift the unit by the damper blade, rotary
knob or actuator.

Fig. 7: Installation example

1.

Install suspension rods and bars (Fig. 7/4) at
the installation location, at a distance of
approx. L+100 mm.

2.

Assemble the ducts (Fig. 7/3) and lead them
up to the installation location of the con-
troller.

3.

Insert seals (Fig. 7/6) between the flanges

Ä

  ‘Attaching sealing tape’ on page 7

 (on-

site).

Observe the air direction arrow (Fig. 7/2)
during installation.

4.

Screw the controller (Fig. 7/1) together with
screws, washers and nuts M10 (Fig. 7/5).

For version with acoustic cladding (EN-D)

Screw connection (Fig. 7/5) with screws
and washers M8;

Insulate ducts up to the acoustic clad-
ding of the controller (on-site).

Installation

 

CAV controllers EN

8

Summary of Contents for CAV controllers

Page 1: ...n open position System pres sure too low Vmin Vmax actuator optional Fig 3 Vmin Vmax actuator 1 Vmax potentiometer 2 Test push button 3 Vmin potentiometer 4 LED status display LED status display LED l...

Page 2: ...hnicians are individuals who have suffi cient professional or technical training in the field they are working in to enable them to carry out their assigned duties at the level of responsibility allo...

Page 3: ...transport damage and complete ness In case of any damage or an incomplete ship ment contact the shipping company and your sup plier immediately Put the product back into its packaging after the deliv...

Page 4: ...Technical data Nominal sizes 200 100 to 600 600 mm Volume flow rate range 39 3500 l s or 140 12600 m h Volume flow rate control range Approx 25 to 100 of the nominal volume flow rate Scale accuracy 4...

Page 5: ...00 300 430 460 330 360 8 5 400 400 400 400 430 460 430 460 13 500 200 500 200 530 560 230 260 8 5 500 250 500 250 530 560 280 310 9 500 300 500 300 530 560 330 360 9 5 500 400 500 400 530 560 430 460...

Page 6: ...00 400 300 430 460 330 360 14 400 400 400 400 430 460 430 460 18 500 200 500 200 530 560 230 260 14 500 250 500 250 530 560 280 310 14 5 500 300 500 300 530 560 330 360 15 5 500 400 500 400 530 560 43...

Page 7: ...ective installation situation information on the straight duct section upstream of the control unit must be observed Duct connections e g branches off the main duct must comply with EN 1505 Horizontal...

Page 8: ...material is not included in the supply package For maintenance or adjustment work the device must be accessible after installation Important If there is a risk that the controller could be subject to...

Page 9: ...s and wiring must be carried out in accordance with the recognised rules of elec trical engineering Observe wiring guidelines and project specific circuit diagrams of the actuators The electrical conn...

Page 10: ...ly fixed and connected to the ducting Ensure that the devices or units as well as the ventilation system are clean and that there are no residual matter and foreign objects Important If there is a ris...

Page 11: ...ng scale Fig 10 2 and fix it with the hexagon socket screw Fig 10 3 No further measurement or adjustment is necessary Setting Vmin Vmax actuators Fig 11 Setting the volume flow rate Factory setting Vm...

Page 12: ...le setting 2 Setpoint value w Vmin 0 V scale setting 4 5 Vmax 10 V scale setting 9 Fig 13 Characteristic actual value signal 1 Scale setting 2 Actual value U Vmin 4 5 V Vmax 9 V Actual value signal Th...

Page 13: ...injury from the use of incorrect replacement parts Incorrect or faulty replacement parts pose a risk to health and safety and their use can cause malfunction damage to property and total failure of e...

Page 14: ...CAV controllers EN 14...

Reviews: