Example for actuator E01, E02:

Given data:

EN 300x200

Vmin 432 m³/h

Vmax 1854 m³/h

Volume flow rate night-time operation 800
m³/h

Volume flow rate day-time operation 1600
m³/h

Settings according to scale Fig. 11:

Vmin potentiometer: 4.5

Vmax potentiometer: 9

Characteristics E03

Fig. 12: Characteristics of the control signal

1

Scale setting

2

Setpoint value w

Vmin: 0 V 

ð

 scale setting 4.5

Vmax: 10 V 

ð

 scale setting 9

Fig. 13: Characteristic actual value signal

1

Scale setting

2

Actual value U

Vmin: 4.5 V
Vmax: 9 V

 Actual value signal

The actual value signal of actuator variant E03
corresponds to the current actuator position in
the scale range and is not a measure of the
actual volume flow rate, since the CAV controller
does not measure the volume flow rate but only
controls it using the aerodynamic forces.

Initial commissioning

 

CAV controllers EN

12

Summary of Contents for CAV controllers

Page 1: ...n open position System pres sure too low Vmin Vmax actuator optional Fig 3 Vmin Vmax actuator 1 Vmax potentiometer 2 Test push button 3 Vmin potentiometer 4 LED status display LED status display LED l...

Page 2: ...hnicians are individuals who have suffi cient professional or technical training in the field they are working in to enable them to carry out their assigned duties at the level of responsibility allo...

Page 3: ...transport damage and complete ness In case of any damage or an incomplete ship ment contact the shipping company and your sup plier immediately Put the product back into its packaging after the deliv...

Page 4: ...Technical data Nominal sizes 200 100 to 600 600 mm Volume flow rate range 39 3500 l s or 140 12600 m h Volume flow rate control range Approx 25 to 100 of the nominal volume flow rate Scale accuracy 4...

Page 5: ...00 300 430 460 330 360 8 5 400 400 400 400 430 460 430 460 13 500 200 500 200 530 560 230 260 8 5 500 250 500 250 530 560 280 310 9 500 300 500 300 530 560 330 360 9 5 500 400 500 400 530 560 430 460...

Page 6: ...00 400 300 430 460 330 360 14 400 400 400 400 430 460 430 460 18 500 200 500 200 530 560 230 260 14 500 250 500 250 530 560 280 310 14 5 500 300 500 300 530 560 330 360 15 5 500 400 500 400 530 560 43...

Page 7: ...ective installation situation information on the straight duct section upstream of the control unit must be observed Duct connections e g branches off the main duct must comply with EN 1505 Horizontal...

Page 8: ...material is not included in the supply package For maintenance or adjustment work the device must be accessible after installation Important If there is a risk that the controller could be subject to...

Page 9: ...s and wiring must be carried out in accordance with the recognised rules of elec trical engineering Observe wiring guidelines and project specific circuit diagrams of the actuators The electrical conn...

Page 10: ...ly fixed and connected to the ducting Ensure that the devices or units as well as the ventilation system are clean and that there are no residual matter and foreign objects Important If there is a ris...

Page 11: ...ng scale Fig 10 2 and fix it with the hexagon socket screw Fig 10 3 No further measurement or adjustment is necessary Setting Vmin Vmax actuators Fig 11 Setting the volume flow rate Factory setting Vm...

Page 12: ...le setting 2 Setpoint value w Vmin 0 V scale setting 4 5 Vmax 10 V scale setting 9 Fig 13 Characteristic actual value signal 1 Scale setting 2 Actual value U Vmin 4 5 V Vmax 9 V Actual value signal Th...

Page 13: ...injury from the use of incorrect replacement parts Incorrect or faulty replacement parts pose a risk to health and safety and their use can cause malfunction damage to property and total failure of e...

Page 14: ...CAV controllers EN 14...

Reviews: