EN
20
Operating manual – dehumidifier / climate manager DH 30 VPR+ / DH 60 VPR+
Technical annex
Technical data
Parameter
Value
Model
DH 30 VPR+
DH 60 VPR+
Dehumidification performance
see dehumidification diagrams
Mains connection
1/N/PE~ 230 V / 50 Hz
Power cable
CEE 7/7 / l = 3.5 m
Power input dehumidification
0.75 kW
1.2 kW
Power input ventilation
88 W
85 W
Nominal/peak current
4.4 A / 15.8 A
7.5 A / 30 A
Heat emission at 15 °C
1.35 kW
2.3 kW
Coefficient of performance (COP *)
2.5
2.9
Refrigerant
R-407C
R-407C
Amount of refrigerant
0.5 kg
0.8 kg
GWP (Global Warming Potential)
1774
1774
Air flow rate (freely blowing, stage 2)
745 m³/h
1,065 m³/h
Sound pressure level (3 m distance)
52 dB(A)
54 dB(A)
Operating range temperature
0 to 40 °C
0 to 40 °C
Setting range relative humidity
30 % to 60 % RH
Max. permissible relative humidity
90 % RH
Max. pump height of the condensate pump
10 m
15 m
Condensation drain hose
ø 5 mm (inside), l = 10 m
Weight
57 kg
90 kg
Dimensions (width x depth x height)
incl. wall holder
787 x 280 x 690 (mm)
1,255 x 280 x 690 (mm)
Standard faceplate
steel, white powder-coated
Minimum distance to walls or other objects:
A: top:
B: bottom:
C: side:
D: front:
12.5 cm
12.5 cm
12.5 cm
12.5 cm
12.5 cm
12.5 cm
12.5 cm
12.5 cm
* The COP is the ratio of the generated cooling capacity or heat output to the electrical power input.
Dehumidification chart
l / 24 h
35
30
25
20
15
10
°C
1)
2)
40 %
50 %
30 %
60 % 70 %
80 %
0
10
20
30
40
50
60
2,15
1,90
1,70
1,50
1,35
1,20
0,80
0,75
0,70
0,65
0,60
0,55
DH 30 VPR
DH 30 VPR+
l / 24 h
35
30
25
20
15
10
°C
1)
2)
40 %
50 %
30 %
60 % 70 %
80 %
0
20
40
60
80
100
120
4,1
3,5
3,1
2,6
2,3
1,9
1,3
1,2
1,1
1,0
0,9
0,8
DH 60 VPR
DH 60 VPR+
No.
Designation
1)
Heat emission in kW at 60 % RH
2)
Power input in kW at 60 % RH