TX3706-UM-EN-02 9
TX3706 • User Manual
2) Fixed Receptacle
Product Code:
Ex Certificate Number:
Ex Certification Code:
TX3706.3.20.xx.xx.xx.xx.xx.xx
CML 15ATEX1143X
IECEx CML 15.0070X
II 2GD
Ex db IIC T4 Gb
Ex db eb IIC T4 Gb
Ex tb IIIC T135 °C Db
-50 °C ≤ Ta ≤ +60 °C
2.3 The following Conditions of Certification and Special
Conditions for Safe Use apply to the above ATEX and IECEx
Certificates:
The following conditions relate to safe installation and/or use of the equipment:
1)
When included, the total capacity of all pin options shall not exceed 100 A, with a maximum
rating per pin of 25 A.
2)
The cable entries and cable used with the TX3706 Falcon 25 Connectors may reach 60°C
above ambient temperatures, therefore, shall be selected accordingly for these temperatures.
3)
The connector arrangement remains flameproof through the first stage of disconnection
which fully disconnects the pins, however, this only applies to circuits with a power factor of
between 0.6 and 1.0. For circuits outside this range, unless for resistive loads only, additional
time delays shall be considered before fully disconnecting the connector even if de-energised.
4)
The stainless steel fixed receptacle, when used in Group I areas, shall only be used in areas
considered to be low risk of mechanical danger or shall be additionally protected from heavy
mechanical impact by installation.
Under certain extreme circumstances, the non-metallic parts of the clamp may store
electrostatic charge and therefore the user/installer shall implement precautions to prevent
the build-up of electrostatic charge, e.g. locate the clamps where a charge-generating
mechanism (such as wind- blown dust) is unlikely to be present. In addition, the clamp shall
only be cleaned with a
damp cloth.
www.trolex.com