Zenica
WATER REQUIREMENTS
The installation must be in accordance with
Water Regulations and Bylaws.
To guarantee activating the heating elements,
the shower must be connected to a mains water
supply with a minimum running pressure of
100kPa (1.0 bar) at a minimum flow rate of
eight litres per minute.
The maximum static pressure must be 1 000kPa
(10 bar).
Note:
If the stated flow rates are not available,
it may not be possible to achieve optimum
performance from the unit throughout the year.
During periods of high ambient temperatures it
may be necessary to select a low power setting
to achieve your preferred shower temperature.
The water supply can be taken from a cold water
storage cistern provided there is a minimum
head of ten metres above the shower head. It
must be an independent supply to the shower
only.
If it is intended to operate the shower at
pressures above the maximum or below the
minimum stated, contact Customer Experience
for advice.
Fig.4
shows a typical system layout.
DO NOT use jointing compounds on any pipe
fittings for the installation.
Isolating
stopvalve
Mains
water
supply
Shower
unit
Mains electric supply
(via double pole switch)
Double
pole
isolating
switch
Separate permanently
connected supply
from consumer unit
Fig.4
Diagrammatic view (not to scale)