background image

7

Table A

CIRCUIT PROTECTION

 

unit 

 cartridge 

 rating 

MCB fuse

 3.0kW 

– 

13A

Table B

Twin and earth PVC insulated cable

CURRENT CARRYING CAPACITY

 

 

 

clipped direct or 

 installed in an 

in conduit 

buried in a non 

 insulated wall  or trunking 

insulated wall

 1.5mm² 

1.5mm² 

1.5mm²

 14A 

16A 

19A

 

Note: Cable selection is dependent 
on derating factors

ELECTRICAL REQUIREMENTS

The installation, supply cable and circuit 
protection must conform with BS7671 (IEE 
wiring regulations) and be sufficient for the 
amperage required.
The following notes are for guidance only:

1

  The unit must only be connected to a 

230 - 240V ac supply.

1.1

  The electrical rating of the unit is shown on 

the rating label

 (fig.2)

 within the unit.

2

  Before making any sort of electrical 

connection within the installation, make 
sure that no terminal is live. If in any doubt, 
switch off the whole installation at the 
consumer unit.

3

   The 3kW rated handwash can be connected 

to a ring main via a 13A fused spur.

3.1

  The electrical supply must be adequate for 

the loading of the unit and existing circuits.

4

  A 30mA residual current device (RCD) must 

be installed in all UK electric circuits. This 
may be part of the consumer unit or a 
separate unit.

WARNING! 

THIS APPLIANCE MUST BE EARTHED

7

Fig.2

Minimum 1.5mm flexible cord in conjunction 
with the cable clamp should be used when using 
top or bottom cable entries.
Twin and Earth flat PVC cable should NOT be 
used for clipped direct installation method.
Surface mounted cable installations should be 
suitably supported by equally spaced clips on 
the wall.

Summary of Contents for T30i

Page 1: ...n the sequence of this instruction book IMPORTANT SAFETY ADVICE The swivel arm supplied with this product is a safety critical part of your shower Failure to use genuine Triton parts may cause injury...

Page 2: ...ny tap or fitting other than those specified This appliance is intended to be permanently connected to the water mains and not connected by a hose set A suitable double pole isolation switch for suppl...

Page 3: ...thin 300mm of the handwash unit as heat can transfer along the pipework and damage components 2 4 DO NOT fit any form of outlet flow control as the outlet acts as a vent for the heater can 2 5 DO NOT...

Page 4: ...DO NOT place items such as soap or shampoo bottles on top of the unit Liquid could seep through the joint between the cover and back plate and possibly damage the sealing rubber If water becomes too...

Page 5: ...it 8 Fitting the unit to the wall 9 Plumbing connections 10 Electrical connections 11 Fitting the swivel arm and cover 12 Commissioning 13 Operating the handwash 14 Operating functions 14 Cleaning 15...

Page 6: ...lamp bottom 4 Mircoswitch 5 Stabiliser valve 6 Pressure Relief Device PRD 7 Can assembly 3kW 8 Thermal Cut Out TCO 9 Outlet pipe 10 Cover Package Contents Handwash unit Cover screw pack 200mm swivel a...

Page 7: ...g 2 within the unit 2 Before making any sort of electrical connection within the installation make sure that no terminal is live If in any doubt switch off the whole installation at the consumer unit...

Page 8: ...ater inlet mains pipework Fig 3 shows a typical system layout DO NOT use jointing compounds on any pipe fittings for the installation Isolating stopvalve Mains water supply Handwash Diagrammatic view...

Page 9: ...fig 4 Procedure Position the unit on the wall and using the backplate as a template mark the two fixing holes fig 5 Drill and plug the wall An appropriate drill bit should be used If the wall is bric...

Page 10: ...be flushed before the unit is fitted This is to remove any debris within the inlet pipework Procedure Turn off the water supply either at the mains stop valve or the isolating stop valve Make sure the...

Page 11: ...rminal marked Neutral cable to terminal marked N Live cable to terminal marked L IMPORTANT When connecting the cable fully tighten the terminal block screws and make sure that no cable insulation is t...

Page 12: ...ol so that it points at the position fig 12 Replace the cover squarely to the backplate and guide into position so that the control locates correctly into the splined spindle Should any difficulty ari...

Page 13: ...l arm then rotate the control fully clockwise to the maximum flow position fig 15 It will take about thirty seconds for a smooth flow of water to be obtained while air and any debris is being disperse...

Page 14: ...ly permanently connected to the handwash unit when not in use OPERATING FUNCTIONS Low Water Pressure Cut out If the water pressure falls below the minimum required for correct operation of the unit po...

Page 15: ...y should be cleaned at regular intervals to prevent build up of deposits from the water supply Blocked spray holes can reduce the water flow to such an extent that it will cause the thermal cut out or...

Page 16: ...oltage The temperature of the water supply can vary from 5 C in the winter to about 20 C in summer with an average of about 12 C The table below shows a scenario of the water temperature you can expec...

Page 17: ...s If it continues contact Triton Customer Experience 4 1 1 Reduce the flow rate 4 2 1 Is water supply mains or tank fed 4 2 2 If tank fed replumb to mains water supply or see 4 2 4 4 2 3 If mains fed...

Page 18: ...ter pressure has dropped below minimum required 6 1 Blocked sprayhead 5 1 1 Wait until the water pressure resumes to normal 6 1 1 Clean or replace sprayhead and then fit new PRD Note Identify cause of...

Page 19: ...ll our electric products are labelled accordingly with the crossed out wheeled bin symbol This indicates for disposal purposes at end of life that these products must be taken to recognised collection...

Page 20: ...should be made by credit debit card excluding American Express or Diners Card Payment can also be made by pre payment of a pro forma invoice by cheque or postal order Telephone orders are based on in...

Reviews: