background image

5

3

Continued

SECTION

Table B

Note: 

Cable selection is dependent on 

derating factors

Twin and earth PVC insulated cable

Current carrying capacity

In conduit

trunking

6mm²

38A

10mm²

52A

16mm²

69A

Installed in an 

insulated wall

6mm²

32A

10mm²

43A

16mm²

57A

Clipped direct

or buried in a 

non-insulated 

wall

6mm²

46A

10mm²

63A

16mm²

85A

6mm2

10mm2

16mm2

*The method below may be used by 

installers to determine the approximate  

size of the incoming cable.

1.

  Measure the width of an individual strand, 

and half that measurment to find 

(r)

,  

e.g: 

1.34mm ÷ 2 = (r) 0.67mm

2.

  Multiply 

(r) x (r)

 x 

3.14,

  

e.g: 

(r)

 

0.67 x (r)

 

0.67 

3.14 = 1.41mm2

3.

  Multiply this by the number of wire strands 

(usually 7), e.g: 

1.41mm2 x 7 = 9.87mm2.

4.

  The number obtained would suggest  

10mm2

 wiring.

*PLEASE NOTE:

 If unsure, consult a qualified Electrician.

6

 

A 45 amp double pole isolating switch with 
a minimum contact gap of 3 mm in both 
poles must be incorporated in the circuit.

6.1

  It must have a mechanical indicator showing 

when the switch is in the OFF position, and 
the wiring must be connected to the switch 
without the use of a plug or socket outlet.

6.2

  The switch must be accessible and clearly 

identifiable, but out of reach of a person 
using a fixed bath or shower, except for the 
cord of a cord operated switch, and should 
be placed so that it is not possible to touch 
the switch body while standing in a bath or 
shower cubicle. It should be readily accessible 
to switch off after using the shower.

7

 

Where shower cubicles are located in any 
rooms other than bathrooms, all socket 
outlets in those rooms must be protected by 
a 30mA RCD.

8

 

The current carrying capacity of the cable 
must be at least that of the shower circuit 
protection 

(see Table B)

.

8.1

  To obtain full advantage of the power 

provided by the shower, use the shortest 
cable route possible from the consumer unit 
to the shower.

8.2

  It is also necessary to satisfy the disconnection 

time and thermal constraints which means 
that for any given combination of current 
demand, voltage drop and cable size, there is 
a maximum permissible circuit length.

9

 

The shower circuit should be separated from 
other circuits by at least twice the diameter 
of the cable or conduit.

9.1

  The current rating will be reduced if the 

cabling is bunched with others, surrounded 
by thermal loft or wall insulation or placed 
in areas where the ambient temperature 
is above 30°C. Under these conditions, 
derating factors apply and it is necessary to 
select a larger cable size.

9.2

  In the majority of installations, the cable 

will unavoidably be placed in one or more 
of the above conditions. This being so, it is 
strongly recommended to use a minimum 
of 10mm cabling throughout the shower 
installation.

9.3

  In any event, it is essential that individual 

site conditions are assessed by a competent 
electrician in order to determine the correct 
cable size and permissible circuit length.

Summary of Contents for Aspirante 8.5kW

Page 1: ...on and keep it for future reference The shower installation MUST be carried out by a suitably qualified person in the sequence of this instruction book Installation and operating instructions Installe...

Page 2: ...t is intended to operate the shower at pressures above the maximum or below the minimum stated b If the unit shows a distinct change in performance c If the shower is frozen 1 7 If it is intended to o...

Page 3: ...pipes or fittings within 300mm of the shower unit as heat can transfer along the pipework and damage components 2 4 DO NOT fit any form of outlet flow control as the outlet acts as a vent for the hea...

Page 4: ...ar to or below the minimum level The drop in pressure may be due to water being drawn off at other points in the house whilst the shower is in use If pressure drops appreciably below the minimum the h...

Page 5: ...7 Plumbing installation 8 Electrical installation 9 Fit to the wall connect shower supplies 9 11 Fitting the cover 12 COMMISSIONING PROCEDURE 13 14 Connecting the PCB cable 14 USER OPERATING INSTRUCTI...

Page 6: ...00 kPa 10 bar Maximum inlet temperature 28 C Minimum inlet temperature 2 C Inlet connection 15mm diameter Outlet connection BSP male thread MATERIALS ABS Backplate cover controls showerhead Acetal Spr...

Page 7: ...m 94mm 300mm ENTRY POINTS DIMENSIONS WATER Left Top Bottom Side Back Right Bottom Side Back CABLE Left Top Bottom Side back Right None Back Back Others Others PLEASE NOTE Deviation from the approved e...

Page 8: ...in any doubt switch off the whole installation at the mains supply and remove the correct fuse 3 The shower must be connected to its own independent electrical circuit IT MUST NOT be connected to a r...

Page 9: ...while standing in a bath or shower cubicle It should be readily accessible to switch off after using the shower 7 Where shower cubicles are located in any rooms other than bathrooms all socket outlet...

Page 10: ...ing to achieve your preferred shower temperature Fig 5 shows a typical system layout Refer to fig 6 for the correct siting of the shower Position the unit where it will NOT be in direct contact with w...

Page 11: ...er hose or a blocked showerhead This may cause the PRD to operate When commissioning the showerhead must be removed from the flexible hose Failure to follow this procedure may cause the PRD to operate...

Page 12: ...e wall This area MUST be left clear when plastering and tiling around the pipework in order to make the nut accessible for future adjustments NOTE An additional stopvalve complying with Water Regulati...

Page 13: ...been chosen the trim can be fitted complete Should either top cable or top pipe entry have been chosen individually the trim has been designed to be separated and the appropriate trim section can be...

Page 14: ...he wall and tighten the retaining screws which hold it to the wall Turn on the mains water supply and check for leaks in the pipework connection to the shower NOTE At this stage no water can flow thro...

Page 15: ...earth conductor must be sleeved The outer sheath of the supply cable must be stripped back to the minimum The use of connections within the unit or other points in the shower circuit to supply power...

Page 16: ...tes correctly minor adjustment may be necessary to align the control and spindle Should any difficulty arise recheck the points above While applying slight pressure to the front cover secure in positi...

Page 17: ...could make the PRD operate Turn on the water supply to the shower at the isolating stop valve Switch on the electricity supply to the shower at the isolating switch Wait until water starts to flow fr...

Page 18: ...fitted into the socket in one way The ribbon cable has a coloured edge which is lowermost when correctly fitted to the socket Guide the cover into position so that the knob spindle locates correctly...

Page 19: ...ll start on the High setting To stop the shower The shower can be stopped by pressing the start stop button When pressed the phased shutdown will begin and water will cease to flow after a few seconds...

Page 20: ...ges in ambient water temperature NOTE The preferred knob position on ECONOMY will give a different temperature to the same position on HIGH To decrease the shower temperature Turn the temperature cont...

Page 21: ...ater pressure the unit automatically restores the power to the elements and returns to the original setting selected Phased shutdown In use every time the Start Stop button is pressed power is switche...

Page 22: ...plate Unscrew the filter cap from the bottom of the inlet pipe Inspect the O ring for damage when the filter cap is removed When cleaning the filter DO NOT use a sharp object as it will cause damage I...

Page 23: ...2 2 1 Check if stop valves are fully open Check if a blockage in the inlet filter 2 3 Increase in ambient water temperature 2 3 1 Readjust flow rate to give increased flow 2 3 2 Select economy power...

Page 24: ...5 1 Thermal safety cut out device has operated Have the unit checked by a suitably qualified engineer or contact Customer Service 4 Pressure relief device has operated water ejected from PRD tube 4 1...

Page 25: ...et S27411001 8 Water Outlet bottom TCO S27411002 9 Main Trimplate White 7054130 Black 7054144 10 Power PCB 7073732 11 Cover assembly including cover PCB Gloss Black S27410606 Gloss White S27410607 Gun...

Page 26: ...der the following schemes Repic Producers take back scheme PTS registration number WEE EJ3466QV Valpak Distributor take back scheme DTS registration number 9659 All our electric products are labelled...

Page 27: ...OF THE ELEMENTS USED HEATER ELEMENTS USED 2 OF THE ELEMENTS USED 0 1 2 H O T HOT COLD To START the shower button A B C or D can be pressed and water will flow from the shower Press A Start Stop and Hi...

Page 28: ...including post code the model number and power rating of the product together with the date of purchase and where applicable details of the particular fault 2 If required the Customer Service Advisor...

Reviews: