18
6.INSTALLATION
The interconnection lines refrigerant is as follows:
- The indoor unit has identified the taking of gas and liquid, with stickers identifying, the
follows:
Gas line: Gas (coolant) / Gas (refrigerant)
Liquid line: liquid (coolant) / Liquid (refrigerant)
- All refrigerant connections, as well as water, are threaded.
- You have to isolate the lines to avoid condensation and heat loss.
- Once you have installed the lines, to empty into the circuit refrigerant indoor unit until a
-1 Kg/cm2 pressure for at least 2 hours.
- The discharge circuit refrigerant and refrigerant charge can be made through service valves
side of the outdoor unit.
- Check for leaks in the circuit refrigerant.
6 26-77:=62<
indoor unit (see paragraph 6.Dimensiones scheme) and since the connections are made .
The indoor unit comes with a dry nitrogen load incorporated. The refrigerant lines of the units
interior are a series of adapters and nuts to ensure proper seal until use.
6 &% #&%
The outdoor unit is shipped with a load of R - 410A applies to a line length
maximum equivalent of 5 meters. For lengths over 5 meters is necessary to add load according
located on the right
6.5 REFRIGERANT SYSTEM CONNECTIONS
General considerations
Connection between indoor and outdoor units
to the table in paragraph 6.7