background image

UPS / Power Module
weight (lbs)

54

UPS / Power Module
weight (kg)

24.5

UPS Shipping dimensions
(height x width x depth /
inches)

16 x 14.8 x 19.8

UPS Shipping dimensions
(height x width x depth /
cm)

40.6 x 37.5 x 50.2

Shipping weight (lbs)

60.5

Shipping weight (kg)

27.5

Cooling method

Fan

UPS housing material

Polycarbonate

ENVIRONMENTAL

Operating Temperature
Range

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius

Storage Temperature
Range

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius

Relative Humidity

0 to 95%, non-condensing

AC mode BTU / hr. (full
load)

347.2

Battery mode BTU / hr. (full
load)

812.9

Audible Noise

Audible Noise < 47dBA At Front Side 1 Meter

COMMUNICATIONS

Communications interface

USB; DB9 Serial; Contact closure

Network monitoring port
description

Supports detailed monitoring of UPS and site power conditions; 2 USB ports, 1 DB9 serial and 1 DB9 contact
closure port (4 total)

PowerAlert software

Included

Communications cable

2 USB and 2 DB9 cables included

WatchDog compatibility

Supports Watchdog application, OS and hard-reboot restart options for remote applications

LINE / BATTERY TRANSFER

Transfer time

2-4 milliseconds

Low voltage transfer to
battery power (setpoint)

151

High voltage transfer to
battery power (setpoint)

282

SPECIAL FEATURES

Cold Start (startup in
battery mode during a
power failure)

Cold-start operation supported

High availability UPS
features

Hot swappable batteries

Summary of Contents for SmartPro SMARTINT2200VS

Page 1: ...offers option for instantaneous power off of UPS and connected equipment in the case of fire or emergency Multi function audible alarms and set of 5 front panel LEDs offer at a glance notification of UPS and line power status Network grade AC surge suppression protects equipment from damage and performance problems resulting from transient surges and line noise Attractive gray color scheme Package...

Page 2: ...ltage Frequency compatibility 50 60 Hz Output voltage regulation line mode 19 8 Output voltage regulation Battery mode 5 Built in UPS output receptacles 8 C13 outlet s 1 C19 outlet s Included output power cables Includes 3 C13 to C14 output power cables Built in controllable switched load banks Three switchable two outlet C13 load banks Output circuit breaker 10A x2 each breaker protects 4 C13 out...

Page 3: ...tween 151 and 176 are boosted by 30 LEDS ALARMS SWITCHES LED Indicators 5 LEDs indicate line power battery power overload voltage regulation and battery low replace status Alarms Audible alarm indicates power failure overload and low battery conditions Alarm cancel operation Power fail alarm can be silenced using alarm cancel switch once silenced alarm will re sound to indicate low battery status ...

Page 4: ...le Noise Audible Noise 47dBA At Front Side 1 Meter COMMUNICATIONS Communications interface USB DB9 Serial Contact closure Network monitoring port description Supports detailed monitoring of UPS and site power conditions 2 USB ports 1 DB9 serial and 1 DB9 contact closure port 4 total PowerAlert software Included Communications cable 2 USB and 2 DB9 cables included WatchDog compatibility Supports Wa...

Page 5: ...tors temperature humidity and contact closure inputs Requires SNMPWEBCARD or switched PDU 1 PDU12IEC Basic PDU Power Distribution Unit Safe reliable power distribution for critical networking equipment 1 P004 006 6 ft 18AWG Power cord IEC 320 C14 to IEC 320 C13 1 SNMPWEBCARD For remote monitoring and control via SNMP Web or Telnet 1 U022 010 10 ft USB2 0 A B Gold Device Cable A Male to B Male 1 WA...

Reviews: