Tripp Lite SmartPro Rackmount SMX1500XLRT2U Features And Specifications Download Page 2

installation requires 2-9USTAND accessory

Large internal batteries support a max load of 1500VA for 7 minutes and a half load of 750VA for 18 minutes

Expandable runtime with BP36V15-2U (limit 1) or with multiple BP36V42-3U rack/tower external battery packs

Maintains regulated 230V nominal output during brownouts and overvoltages from 151 to 282V

Includes 8 UPS supported outlets arranged in 3 individually controllable load banks (2 outlets per bank) that can be powered off and back

on again via software interface

IEC320-C14 input connection accepts a variety of detachable cordsets to match country or site-specific wall receptacles

PowerAlert UPS monitoring and unattended shutdown software enables configurable network broadcast messaging, email notification,

event logging and running user-defined script commands.

Offers simultaneous monitoring by up to 2 directly-connected devices through included USB and DB9 interface ports, or the monitoring by

any number of additional servers over IP with included PowerAlert monitoring software.

Communications ports support messaging of UPS and line power status, including on-battery, low-battery, power restored, AC line voltage,

DC battery voltage and remaining battery capacity

Emergency Power Off (EPO) interface with cable

Supports timed inverter shutoff after unattended shutdown, activate self-test and UPS output power control for delayed or immediate reboot

of connected devices

Supports Tripp Lite's WatchDog software application to restore operation to locked equipment through soft reboot of application, OS or hard

power off/on reboot of connected equipment - ideal for unattended kiosk applications (requires optional WATCHDOGSW)

Built-in accessory slot supports SNMP with optional SNMPWEBCARD adapter

Emergency Power Off (EPO) interface with cable

Multi-function audible alarms and set of 5 front panel LEDs

Network-grade AC surge suppression

Attractive all-black color scheme

UPS battery set ships fully assembled, no time consuming connection of internal batteries by user is necessary

Specifications

OUTPUT

Output Volt Amp Capacity
(VA)

1500

Output kVA capacity (kVA)

1.5

Output Watt Capacity
(watts)

1000

Output kW capacity

1

Output power factor

0.7

Nominal Output Voltage(s)
Supported

230V

Nominal Voltage details

230v nominal inverter output voltage

Frequency compatibility

50 / 60 Hz

Output voltage regulation
(line mode)

-17%, +8%

Output voltage regulation
(Battery mode)

+/- 5%

Built-in UPS output
receptacles

8 C13 outlet(s)

Included output power
cables

Includes 2 C13 to C14 output power cables

Built-in controllable
switched load banks

Three switchable two-outlet C13 load banks

Output AC waveform (AC
mode)

Sine wave

Summary of Contents for SmartPro Rackmount SMX1500XLRT2U

Page 1: ... that are individually switchable via software interface to reboot select equipment on demand or shed less significant loads to extend battery runtime for more critical equipment Supports simultaneous remote monitoring of UPS and site power conditions via built in USB and DB9 monitoring ports Includes PowerAlert UPS monitoring and unattended shutdown software with complete cabling Built in accesso...

Page 2: ...rgency Power Off EPO interface with cable Supports timed inverter shutoff after unattended shutdown activate self test and UPS output power control for delayed or immediate reboot of connected devices Supports Tripp Lite s WatchDog software application to restore operation to locked equipment through soft reboot of application OS or hard power off on reboot of connected equipment ideal for unatten...

Page 3: ...ont panel battery access door Battery replacement description Hot swappable user replaceable batteries VOLTAGE REGULATION Voltage regulation description Automatic voltage regulation AVR maintains line power operation with an input voltage range of 151 to 282 Overvoltage correction Input voltages between 245 and 282 are reduced by 12 Undervoltage correction Input voltages between 181 and 199 are bo...

Page 4: ...s in primary form factor height x width x depth cm 8 9 x 44 4 x 34 3 Installed whole system dimensions in secondary form factor height x width x depth cm 44 4 x 8 9 x 34 3 Rack Height 2U Secondary form factor Tower requires 2 9USTAND Installed whole system dimensions in secondary form factor height x width x depth inches 17 5 x 3 5 x 13 5 UPS dimensions in secondary form factor height x width x de...

Page 5: ...or remote applications LINE BATTERY TRANSFER Transfer time 2 4 milliseconds Low voltage transfer to battery power setpoint 151 High voltage transfer to battery power setpoint 282 SPECIAL FEATURES Grounding lug Back panel grounding lug Cold Start startup in battery mode during a power failure Cold start operation supported High availability UPS features Hot swappable batteries Green high efficiency...

Page 6: ...ring and control via SNMP Web or Telnet 1 U022 010 10 ft USB2 0 A B Gold Device Cable A Male to B Male 1 WATCHDOGSW WatchDog Service Monitoring Reboot Software 1 2 9USTAND Enables Tower Placement of Rackmount UPS Systems 1 2POSTRMKITWM Enables 2 Post Rackmount or Wallmount Installation of Select Rackmount UPS Systems 1 MODBUSCARD For remote monitoring and control via MODBUS protocol 1 More informa...

Reviews: