9. Control Panel
9.3.8.2 Historic Events
More detailed information is displayed in the ‘History Events’ screen. In addition to the Power Module ID number and the text summary, the time
the event occurred and two data line codes are shown. Up to 500 events are stored in the ‘History Events’ screen. Refer to tables 9.6 – 9.8 for a
complete list of text summaries and explanations.
9.3.8.3 Reset All Events
WARNING
Tripp Lite does not recommend this action. Upon reset, diagnostic information will be lost and any warranty claims may
be affected.
The maintenance password (default 9999) is required to enter the “Reset All Events” screen. Select “Yes” to reset the events log. The data will
not be preserved once reset is selected.
9.4 Text Summaries and Explanations
FAULTS
LCD Display Text
Explanation
Fault ! Bus Over Voltage
DC bus voltage is too high
Fault ! Bus Under Voltage
DC bus voltage is too low
Fault ! Bus Voltage Unbalance
DC bus voltage is imbalanced
Fault ! Bus Short
DC bus has a short
Fault ! Bus Soft Start Time Out
Low DC bus voltage within specified duration – rectifier unable to start
Fault ! Inverter Soft Start Time Out
Inverter bus voltage cannot reach desired voltage within specified duration
Fault ! Inverter Voltage Over
Inverter voltage over (peak value): 385V for 220/230V output; 395V for 240V output
Fault ! Inverter Voltage High
Inverter voltage is too high
Fault ! Inverter Voltage Low
Inverter voltage is too low
Fault ! R Inverter Voltage Short
R phase inverter output is shorted
Fault ! S Inverter Voltage Short
S phase inverter output is shorted
Fault ! T Inverter Voltage Short
T phase inverter output is shorted
Fault ! RS Inverter Voltage Short
R-S inverter output is shorted
Fault ! ST Inverter Voltage Short
S-T phase inverter output is shorted
Fault ! TR Inverter Voltage Short
T-R phase inverter output is shorted
Fault ! Inverter R Negative Power
R phase inverter output negative power over range
Fault ! Inverter S Negative Power
S phase inverter output negative power over range
Fault ! Inverter T Negative Power
T phase inverter output negative power over range
Fault ! Overload Fault
UPS is heavily overloaded
Fault ! Battery Fault
Battery is reversed
Fault ! Over Temperature
The UPS operating temperature is outside acceptable limits
Fault ! CAN Fail
CAN communication failure
Fault ! TRIGO Fault
Synchronized trigger signal fault
Fault ! Relay Fault
Inverter relay fault
Fault ! Line SCR Fail
Line SCR short circuit
Fault ! EEPROM Fault
EEPROM operation error
Fault ! Parallel Cable Loosen Fault
Parallel cable between Power Modules is loose
Fault ! DSP MCU Stop Communicate
DSP communication loss
Fault ! Bypass Temperature Fault
Bypass operating temperature is outside acceptable limits
Fault ! Bypass SCR Fault
No bypass voltage measured
Line Fail
Utility lost or outside acceptable limits
Line Restore
Utility present within acceptable limits